Allen-Bradley 1606 Reference Manual

Allen-Bradley 1606 Reference Manual

Switched mode power supplies
Hide thumbs Also See for 1606:

Advertisement

Quick Links

Reference Manual
Bulletin 1606 Switched Mode Power Supplies
Catalog Number: 1606-XLE480FP
Index
1. Intended Use .......................................................3
2. Installation Requirements ...................................3
3. AC-Input ...............................................................4
4. DC-Input...............................................................5
5. Input Inrush Current ...........................................5
6. Output .................................................................6
7. Hold-up Time.......................................................8
8. DC-OK Relay Contact ..........................................8
9. Efficiency and Power Losses................................9
10. Lifetime Expectancy and MTBF.........................10
11. Functional Diagram...........................................10
12. Terminals and Wiring........................................11
13. Front Side and User Elements...........................12
14. EMC....................................................................13
15. Environment ......................................................14
16. Protection Features ...........................................15
17. Safety Features ..................................................15
18. Dielectric Strength ............................................16
19. Certifications......................................................16
Terminology and Abbreviations
• PE and
symbol-PE is the abbreviation for Protective Earth and has the same meaning as the symbol
• Earth, Ground-This document uses the term "earth" which is the same as the U.S. term "ground".
• T.b.d.-To be defined, value or description will follow later.
• 3AC 400V-A figure displayed with the AC or DC before the value represents a nominal voltage with standard tolerances (usually ±15%)
included. E.g.: DC 12V describes a 12V battery whether it is charged (13.7V) or discharged (10V).
• 230Vac-Afigure with the unit (Vac) at the end is a momentary figure without any additional tolerance included.
• 50Hz vs. 60Hz-Unless otherwise stated, AC 230V parameters are valid at 50Hz mains frequency.
• may-A key word indicating flexibility of choice with no implied preference.
• shall-A key word indicating a mandatory requirement.
• should-A key word indicating flexibility of choice with a strongly preferred implementation.
P
a
g
e
20. Physical Dimensions and Weight ..................... 17
21. Accessories ........................................................ 18
22. Application Notes............................................. 19
22.1. Peak Current Capability ...........................19
22.2. Back-feeding Loads ..................................19
22.3. External Input Protection .........................20
22.4. Output Circuit Breakers ............................20
22.6. Parallel Use for Redundancy ....................21
22.7. Series Operation .......................................22
22.9. Charging Batteries ....................................23
22.10. Operation on Two Phases ........................23
22.12. Mounting Orientations ............................24
P
a
g
e
.

Advertisement

Table of Contents
loading

Summary of Contents for Allen-Bradley 1606

  • Page 1: Table Of Contents

    Reference Manual Bulletin 1606 Switched Mode Power Supplies Catalog Number: 1606-XLE480FP Index 1. Intended Use ............3 20. Physical Dimensions and Weight ..... 17 2. Installation Requirements ........3 21. Accessories ............18 3. AC-Input ...............4 21.1. 1606-XLC Wall Mounting Bracket....18 4.
  • Page 2 The 1606-XLE are cost optimized power supplies without compromising quality, reliability and Adjustment range 48 - 56V performance. The 1606-XLE series is part of Rockwell Output current at 48V, amb <60°C Automation's family of power supplies. The most at 48V, amb <45°C outstanding features of the 1606-XLE480FP are its high 8.6A...
  • Page 3: Intended Use

    • The unit is suitable for use in Class I Division 2 Groups A, B, C, D locations All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 4: Ac-Input

    100Vac, 120Vac 230Vac 0.95 0.85 Output Current Output Current 0.75 10 11 10 11 All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 5: Dc-Input

    Bulletin 1606 Switched Mode Power Supplies 4. DC-Input Do not operate this power supply with DC-input voltage. Use the 1606-XLE480FP-D instead. 5. Input Inrush Current An active inrush limitation circuit limits the input inrush current after turn-on of the input voltage and after short input voltage interruptions.
  • Page 6: Output

    The typical value is about 57.0V (in “single use” mode). All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 7 Output Voltage (dynamic behavior, < 15ms) Output Current Normal Normal Short -circuit operation operation Adjustment Range Output Current All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 8: Hold-Up Time

    Fig. 8-1 DC-ok relay contact behavior 0.9* V < > 100ms open closed open closed All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 9: Efficiency And Power Losses

    Fig. 9-4 Losses vs. input voltage at 48V, 10A, 10A, typ. typ. Efficiency Power Losses Input Voltage Input Voltage 264Vac 264Vac All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 10: Lifetime Expectancy And Mtbf

    Shut- Voltage DC-ok Manager down Protection Output Voltage DC-ok DC-ok Monitor Relay Contact All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 11: Terminals And Wiring

    Power Power Supply Supply Load Load Output Output Output Output max 25A! continuous All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 12: Front Side And User Elements

    4% higher than at nominal load. See also section 24.5. A missing jumper is equal to a “Single Use” mode. All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 13: Emc

    **) for information only, not mandatory for EN 61000-6-3 All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 14: Environment

    Operational temperature is the same as the ambient temperature and is defined as the air temperature 2cm below the unit. **) Do not energize in the presence of condensation. ***) Higher levels allowed when using the 1606-XLC wall mounting bracket. Fig. 15-1 Output current vs. ambient temp.
  • Page 15: Protection Features

    0.46mA / 1.08mA 264Vac, 50Hz, TN-,TT-mains / IT-mains double or reinforced insulation All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 16: Dielectric Strength

    Product certification information (including Certificates and Declarations of Conformity) can be found at www.ab.com/certification. All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 17: Physical Dimensions And Weight

    Installation Clearances See section 2. Fig. 20-1 Front view Fig. 20-2 Side view All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 18: Accessories

    This bracket is used to mount the power supply onto a flat surface without a DIN rail. All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 19: Application Notes

    The maximum allowed feed-back-voltage is 63Vdc. The absorbing energy can be calculated according to the built-in large sized output capacitor which is specified in section 6. All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 20: External Input Protection

    Don’t forget to consider twice the distance to the load (or cable length) when calculating the total wire length (+ and – wire). All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 21: Parallel Use To Increase Output Power

    22.5. Parallel Use to Increase Output Power Unit A 1606-XLE480FP power supplies can be paralleled to increase the output power. The output voltage of all power supplies shall be adjusted to the same value (±100mV) in “Single use” mode with the same load conditions on all units, or the units can be left with the factory settings.
  • Page 22: Series Operation

    Hiccup mode (see section 6). All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 23: Charging Batteries

    53.3°C (in the middle of the right side of the power supply with a distance of 2cm) Temperature outside enclosure: 25.3°C Temperature rise: 28.0K All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 24: Mounting Orientations

    60°C Fig. 22-8 Output Current Mounting Orientation E (Horizontal ccw) Ambient Temperature 60°C All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise. Rockwell Automation Publication 1606-RM043A-EN-P — March 2014...
  • Page 26 Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http:// literature.rockwellautomation.com/idc/groups/literature/documents/du/ra-du002_-en-e.pdf. Publication 1606-RM043A-EN-P — March 2014 Copyright © 2014 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.