The status of the software zones can be displayed in two ways, Option 2
(PTREAD) of the Read Status menu or Option 1 (RPTS) of the Special
Function menu. By entering Option 2 of the Read Status menu, the user
can obtain point reports displayed to the 80-character display and/or CRT
terminals. This option will display information on the status of any
software-defined zone (as well as detectors, modules, or annunciators),
including CBE and CCBE equations programmed for reverse activated
software zones.
PRESS 1=SYS, 2=PTREAD, 3=ALM, 4=TBL, 5=DIS, 6=MONON, 7=CTLON
ENTER LXX (D/M) YY, ZXXX OR AXXPYY FOR PT. STATUS (BCKSPC TO ABORT):Z201
NORMAL REVERSE ZONE
OR ( )
OR (N1Z1 N2Z2 N3Z1 N4Z1 N5Z1 N6Z1 N7Z1 N8Z1 N9Z1)
By entering Option 1 (RPTS) of the Special Function menu, the user can
obtain a printed report for the status of all installed points. Once Option 1
has been selected, Option 2 (POINT) must be selected. This option will
print out status information of all installed points for the particular
IFC-1010/2020 panel the report is requested from.
IFC Networking—Metasys Intelligent Fire Network
:2
67