Chapter 4 Parameter Functions
Multi-function output direction
Control mode
VF
Settings
 This parameter is used for bit-wise setting. If the corresponding bit is 1, the multi-function
output is set as reverse direction.
Low-pass filtering time of keypad display
Control mode
VF
Settings
 This parameter can be set to reduce the fluctuation of the readings on the keypad.
Maximum output voltage for pressure feedback
Control mode
VF
Settings
Minimum output voltage for pressure feedback
Control mode
VF
Settings
 This parameter defines the pressure feedback output voltage type.
 If the pressure feedback has a bias, can adjust this parameter to eliminate the bias.
Type of Pressure Feedback Selection
Control mode
VF
Settings
 PO (Pressure Feedback) terminal: Add a current-fed pressure feedback (4~20mA)
The following are required when using it:
Switch the SW100 on the I/O board to "I".
Set Pr03-12 = 0 (4~20mA)
Set Pr00-36 =1 (Enable detection of the pressure feedback disconnection)
HES Series
FOCPG
FOCPM
0~65535
FOCPG
FOCPM
0.001~65.535 seconds
FOCPG
FOCPM
5.0~10.0 V
FOCPG
FOCPM
0.0~2.0V
FOCPG
FOCPM
0:
Current
1:
Voltage
4-38
Factory default: 0
Factory default: 0.100
Factory default: 10.0
Factory default: 0.0
Factory default: 1