Chapter 5 Methods of Anomaly Diagnosis
Display Code
Alarm reset
Once the issue that tripped the system and triggers the alarm is eliminated, one can resume the
system to normal status by pressing the RESET key on the digital keypad (as shown in the figure)
to set the external terminal to "Anomaly reset command" and sending the command by turning on
the terminal or via communication. Before any anomaly alarm is resolved, make sure the operation
signal is at open circuit status (OFF) to avoid immediate machine running upon anomaly reset that
may case mechanical damage or personnel casualty.
HES Series
Description of Anomaly
Auto tuning error (AuE)
Oil pump runs reversely (Prev)
Oil shortage (noil)
1. Check if the wiring of the motor is correct.
2. Check if the motor's parameter settings are
correct.
1. Check if there is any zero shift at the
pressure sensor.
2. Check if the wiring of pressure sensor is
correct.
1. Check the amount of oil in the oil tank.
2. Check if any leakage at hydraulic circuit.
3. If there's a suction filter installed at the oil
inlet, check if that suction filter is blocked up.
F
H
U
JOG
RUN
5-8
Troubleshooting
KPV-CE01
EXT PU
PU
STOP
RESET