Chapter 4 Parameter Functions
Example: If the pressure sensor indicates 250bar at 10V. If the controller's maximum pressure
of 140bar corresponds to 10V, then Parameter 00-07=140. Set the pressure as 140bar by
using the controller, the voltage value shown on the display is about 56.0 (140/250 *
100%). Enter this value into the Parameter 00-14. Then set the pressure as 70bar on the
controller, and now the value displayed on the keypad is about 28.0 (70/250 * 100%).
Enter this value to the Parameter 00-15. Then set the pressure as 0 bar on controller, and
the voltage value shown on the keypad is about 0.0 (0/250 * 100%). Enter this value in the
Parameter 00-16.
Percentage of the flow command value (Max)
Control mode
VF
Settings
Percentage of the flow command value (Mid)
Control mode
VF
Settings
Percentage of the flow command value (Min)
Control mode
VF
Settings
 To set these parameters, it is necessary to set Parameter 00-09 as 1
 Parameter 00-04 = 25 for QI input voltage
Send the 100% flow rate through the controller and then check the multi-function display page
to enter this value into 00-17
Send the 50% flow rate through the controller and then check the multi-function display page to
enter this value into 00-18
Send the 0% flow rate through the controller and then check the multi-function display page to
enter this value into 00-19
P gain 1
P gain 2
P gain 3
Control mode
VF
Settings
I integration time 1
I integration time 2
I integration time 3
Control mode
VF
Settings
Differential gain
Differential gain 2
Differential gain 3
Control mode
VF
Settings
 This parameter is functional only when Bit0 and Bit2 = 1 at Pr00-38.
Pressure stable region
Control mode
VF
Settings
HES Series
FOCPG
FOCPM
0.0~100.0%
FOCPG
FOCPM
0.0~100.0%
FOCPG
FOCPM
0.0~100.0%
FOCPG FOCPM
0.0~1000.0
FOCPG FOCPM
0.00~500.00 seconds
FOCPG FOCPM
0.0~100.0 %
FOCPG FOCPM
0~100%
4-16
Factory default: 100.0
Factory default: 50.0
Factory default: 0.0
Factory default: 50.0
Factory default: 2.00
Factory setting: 0.0
Factory default: 25