Flux-Weakening Voltage Level
Control mode
Settings
The function of Pr01-38 is to adjust the flux-weakening voltage level.
Adjust this parameter to use the voltage to lower the motor's current when necessary. If you
make the current too low, there's a current distortion.
The maximum DC BUS output voltage is the highest setting value of Pr01-38.
FOCPG FOCPM
0 ~100V
Chapter 4 Parameter Functions
4-31
HES Series
Factory default: 10V