4.
Set Pr01-07 as 1 and then press the RUN button on the keypad. The auto tuning process
for the motor is carried out immediately. (Note: the motor starts running).
5.
After the process is finished, check if the motor's parameters (Pr01-13 ~Pr01-16) have
been automatically entered with the measurement data.
6.
Equivalent circuit of the motor
NOTE
* When the static tuning (Pr01-07 = 2) is used, you must enter the no-load current to the motor. It is generally 20 to
50% of the rated current.
If the parameter is set as 5, it will perform the parameter automatic tuning for the synchronous
motor. In this case, press the [Run] button to perform the automatic measurement operation
immediately. After the measurement is complete, the values are filled into Parameters 01-22
(Rs), 01-23 & 24 (Ld & Lq), 01-25 (Back EMF of the synchronous motor), respectively.
Synchronous motor AUTO-Tuning procedure: (static measurement)
1.
All parameters of the Hybrid Servo Controller are set to factory settings and the motor is
connected correctly.
2.
Set the rated current 01-17, rated power 01-18, rated speed 01-19, and number of poles
01-20 of the motor with correct values, respectively. For the acceleration/deceleration
time, set the values according to the motor's capacity.
3.
Set Parameter 01-07 as 5 and then press the RUN button. The auto tuning process for
the motor is carried out immediately. (Note: the motor starts running slightly).
4.
After the process is finished, check if the motor's parameters (parameters 01-22 ~ 01-25)
have been automatically entered with the measurement data.
If the Parameter is set as 4, the automatic measurement of the angle between magnetic pole
and the PG origin for the synchronous motor is performed. In this case, press the [Run] button
to immediately perform automatic measurement. The measured data will be entered into
Parameter 01 -27.
Auto-Tuning process for Synchronous Motor of the Angle between Magnetic Poles and PG
Origin:
1.
Set Pr01-07 as 5 <Rolling test for PM motor> and run this setting. Or input the correct
vales to Pr01-03, Pr01-17 to Pr01-25.
2.
Before tuning, it is recommended to separate the motor and the load.
3.
Set Pr01-07 as 4 and then press the RUN button on the keypad. The auto tuning process
for the motor is carried out immediately. (Note: the motor starts running).
4.
After the process is complete, check if the values for the angle between magnetic poles
and PG origin have been automatically entered in Pr01-27.
Rs
I
Pr .01-16
Pr. 01-13
V
S
Motor equivalent circuit used by VJ
4-25
Chapter 4 Parameter Functions
Lx
Lm
Pr.01-15
HES Series
Rr
Pr. 01-14