Chapter 4 Parameter Functions
Rated current of the induction motor (A)
Control mode
Settings
 To set this parameter, the user can set the rated motor current range shown on the motor's
nameplate. The factory default is 90% of the rated current of the Hybrid Servo Controller.
For example: For the 7.5HP (5.5kW) motor, the rated current is 25, the factory settings: 22.5A.
The customers can set the parameter within the range 10 ~ 30A.
25*40%=10
Rated power of the induction motor
Control mode
Settings
 Set the motor's rated power. The factory default value is the power of the Hybrid Servo
Controller.
Rated speed of the induction motor
Control mode
Settings
 This parameter sets the rated speed of the motor. It is necessary to refer to the specifications
shown on the motor's nameplate.
Number of poles of the induction motor
Control mode
Settings
 This parameter sets the number of motor number of poles (odd number is not allowed).
No-load current of the induction motor (A)
Control mode
Settings
 The factory default is 40% of the rated current of the Hybrid Servo Controller.
Stator resistance (Rs) of the induction motor
Control mode
Rotor resistance (Rr) of the induction motor
Control mode
Settings
Magnetizing inductance (Lm) of the induction motor
Control mode
Total leakage inductance (Lx) of the induction motor
Control mode
Settings
Rated current of the synchronous motor
Control mode
Settings
 The user can set the rated current shown on the synchronous motor's nameplate.
HES Series
FOCPG
40~120% of the rated driving current
25*120%=30
FOCPG
0 – 655.35kW
FOCPG
0~65535
FOCPG
2~20
FOCPG
0~ Default value of Parameter 01-08
FOCPG
FOCPG
0~65.535Ω
FOCPG
FOCPG
0.0~6553.5mH
FOCPM
0~655.35 Amps
4-26
Unit: Ampere
Factory default: #.##
Factory default: #.##
Factory default:
1710 (60Hz 4-pole)
1410 (50Hz 4-pole)
Factory default: 4
Unit: Ampere
Factory default: 40
Factory default: #.##
Factory default: #.##
Factory default: #.##
Factory default: #.##
Factory default: 0.00