Delta HES Series Instructions For Use Manual page 50

Hybrid energy saving system
Hide thumbs Also See for HES Series:
Table of Contents

Advertisement

Chapter 3 Flow of machine AdjustmentHES Series
Confluence Machine Tuning Procedure
Follow the associated descriptions in Chapter 2 to lay out the wiring.
Follow steps 1 and 2 described above to enter the electrical codes for the master/slave
machines. Then proceed with the steps below.
Master setting
Set the Parameter 03-06 = 1
Multifunction Output 2 (MO1)
Setting value
of Pr. 03-06
Connect the Master's MO1 output terminal to the Slave's SON terminal and Master's MCM
terminal to the Salve's COM terminal.
For the firmware version 2.03 and above, it is not necessary to perform the two steps
described above
Set the Parameter 03-13 = 1
Confluence Master/Slave Selection
Setting value
of Pr. 03-13
Set the Parameter 03-14
Slave's proportion of the Master's flow
Setting value
of Pr. 03-14
For firmware version 2.03 and above, the Parameter 03-17 can be configured to determine
the activation level for the Slave
Slave's activation level
Setting value
of Pr. 03-17
Slave setting
Parameter 01-01=1
Source of operation command
Setting value
of Pr. 01-01
1: Operation indication
0: No function
1: Master 1
2: Slave/Master 2
3: Slave/Master 3
0.0~6553.5%
0~100%
0: Operation by using the digital keypad
1: Operation by using the external terminals. The Stop button on the
keypad is disabled.
2: Communication using RS-485. The Stop button on the keypad is
disabled
3-12