EMS INTRODUCTION AND SET UP
Step 12:
If you want to use force charge,
set Enable here.
Step 14:
Set the UPS Reserve SOC, it
means how much battery energy left for
UPS function.
Step 16:
If you use CT meter, please set
CT meter enable and the relevant ratio
Step 18:
Click System in the setting
menu. Click Date &Time and set up the
date and time.
Step 13:
Set the charge and discharge
time.
Step 15:
Click Safety in the setting
menu. Set safety standard.
AS4777.2 for Australia, VDE4105/11.18
for Germany, CEI0-21 for Italy, G98/G99
for Britain, NRS097-2-1 for South Africa,
RD1699 for Spain. For other details
please find in Section 9.2.
For Volt-var/watt function in South
Australia please choose AS4777-SA.
Step 17:
If you use UPS function, please
set the mute as YES in UPS System
interface and the relevant Frequency.
Step 19:
Click Ethernet to set the IP
address. DHCP mode means that setup IP
address is set up automatically.
If you want to set up the IP address
manually, please choose manual mode
45
46
NOTE:
It is needed to set the following 3 parameters for manual mode:
IP Address: IP address;
Subnet Mask: Subnet mask;
Default Gateway: Default gateway;
Automatic display one parameter:
MAC Address: display MAC Address.
Step 20:
Click Language to set language
4.2.4.2 Additional Function Setting
A.
If you use Backup box, please set as below:
Step 1:
Click Enable to set yes.
B.
If external device will dispatch the system, please set as following steps:
Step 1:
Please go to the function menu,
choose "ModBus" and press enter.
EMS INTRODUCTION AND SET UP
Step 21:
Make sure all the following
number is correct.
Step 2:
Set the priority of the load, L1>
L2>L3
Step 2:
Please set Modbus enable as
yes.