Common Start/Stop Sequence, Diesel Or Gas Engine - Deif MPC-1 Programming Manual

Multi power controller
Table of Contents

Advertisement

Gas delay
21s
08 s
Starter time
05s
03 s
Start pause
10s
time
10 s
Gov. Down
OFF
bef.
Start
OFF

6.5 Common start/stop sequence, diesel or gas engine

DISPLAY
Facto-
ry
Set
Cool down
030s
time
180 s
Monitoring
08s
Delay
15 s
Firing speed
15Hz
Reached: f>
15Hz
Pickup
ON
ON
Nom. Speed
1500
Gen. 1/min
1500
Pickup:
0030
Number
of cogs
0030
Mains break.
ON
Free
Start engine
ON
Page 34 of 35 Tlf. (+45) 9614 9614 · Fax:(+45) 9752 4720 · E-mail: deif@deif.com
0...99 s. Delay of gas supply after enga-
gement of start motor.
Must be a few seconds longer as the "Ign.
delay".
0...99 s. Start motor engagement time.
1...99 s. Delay between start attempts.
ON/OFF. If ON is chosen, a 4 sec. signal
"speed down" will be sent to governor, before
start is attempted.
Commis-
DESCRIPTION
sioning
value
0...800 s. Cool down time (idle run) after
normal stop or fail with class F2. Timer
starts when generator breaker is opened.
1...99 s. Time delay from firing speed is
reached until engine alarm and shutdown
functions are activated.
15...70 Hz. Firing speed selection, related
to generator frequency.
ON/OFF. Selects if the speed pickup input
is to be active. if NO the firing speed
detection will use the generator frequency.
0...5000. Nominal generator RPM.
0...9999. No of cogs (teeth) on the flywheel
(normal pickup measuring point).
ON/OFF. If ON and "Auto 1" or "Auto 2" is
activated, the engine will start automatically
and close the generator breaker if the "mai-
ns breaker free" input is switched OFF. This
enables automatic island operation during
mains failure.