Deif MPC-1 Programming Manual page 29

Multi power controller
Table of Contents

Advertisement

Analog out
X4X5
100% =
0000
Parameters: See next page.
The following parameters are available:
Parameter
Function
no.
00
No output
01
Generator power
02
Generator cos
(-070...+070)/100
03
Generator frequency
(Hz*100)
04
Generator reactive
power
05
Available power for
parallel running
generators
06
Total power for parallel
running generators
07
Temperature T1 ( o C)
term. 108-110
08
Temperature T2 ( o C)
term. 111-113
09
Temperature T1 ( o F)
term. 108-110
10
Temperature T2 ( o F)
term. 108-110
Programming manual MPC-1
0...9994. Value equal to 20mA output (NO-
TE: For frequency output, key in value equ-
al to f x 100. The output cannot handle de-
cimals).
Description
0% = Lowest power (kW). Can be
negative.
100% = Highest power (kW)
0% = Lowest factor, e.g. –010 equals -
0.1
100% Highest factor, e.g. 010 equals
+0.1
0% = Lowest value, e.g. 0000 equals
00.00 Hz
100% = Highest value, e.g. 7000 equals
70.00 Hz
0% = Lowest value (kvar). Can be
negative
100% = Highest value.
0% = Lowest value (kW). Can be
negative
100% = Highest value.
0% = Lowest value (kW). Can be
negative
100% = Highest value.
0% = Lowest value, e.g. 0000 equals
000 o C.
100% = Highest value, e.g. 0255 equals
255 o C
0% = Lowest value, e.g. 0000 equals
000 o C.
100% = Highest value, e.g. 0255 equals
255 o C
0% = Lowest value, e.g. 0000 equals
000 o F.
100% = Highest value, e.g. 0255 equals
255 o F
0% = Lowest value, e.g. 0000 equals
000 o C.
100% = Highest value, e.g. 0255 equals
255 o F
4189340103E

Advertisement

Table of Contents
loading

Table of Contents