Freq. Controller
ON
Freq.controller
Ramp
05Hz/s
Freq. Controller
Nz = 0.10 Hz
Freq. Controller
Time pulse>080ms
Freq. Controller
Gain.Kp = 15.0
2.7.2

Frequency controller analog output (Option B1/B3)

DISPLAY
Base pos. freq.
10%
P-amplification
f Kpr
100
Delay time
f Tn
02.5s
2.7.3

Voltage controller relay outputs (standard)

DISPLAY
Volt. controller
ON
Page 10 of 35 Tlf. (+45) 9614 9614 · Fax:(+45) 9752 4720 · E-mail: deif@deif.com
ON
05
Hz/s
0.05
Hz
065
ms
15.0
Factory
Commis-
set
sioning
value
10%
100
02.5s
Factory
Commis-
set
sioning
value
ON
Frequency controller ON/OFF.
"cursor " selects ON/OFF value.
"select" enters the chosen value.
2...50 Hz/s. Frequency ramp
speed
0.05...1.00 Hz neutral zone.
Island operation: Frequency within
f nom. ± neutral zone causes no
controller action.
Dynamic synchronisation: Max. dif-
ferential frequency = neutral zone
value.
10...250 ms. Min. impulse time for
controller relay outputs.
Min. Time required for the engine
governor to react on impulse.
1.0...99.9 amplification factor for
frequency controller.
The Kp affects the ON time for the
relay output. Kp ­ = ON time ­.
DESCRIPTION
0...50 %. Idle run genset frequency
at startup. Relates to system base
frequency.
0...500. P-band factor for controller
function
0...99s. I-time factor for controller
DESCRIPTION
Voltage controller ON/OFF.
"cursor " selects ON/OFF value.
"select" enters the chosen value.