Deif MPC-1 Programming Manual page 32

Multi power controller
Table of Contents

Advertisement

NOTE: If load sharing is to be successful, the parameters "Nominal frequency" and
"Parallel run ON" must be set to equal value in all MPC-1 units.
DISPLAY
Load dependent
Start/stop
ON
Start point
Gen.
0015kW
Start delay
005s
Hysteresis
Main/Isl.op. 005kW
Available power
Main op.0030kW
Startpriority
(0=run.hours) 00
Available power
Island op.0030kW
Start delay
Island op. 001s
Stop delay
Island op. 001s
Page 32 of 35 Tlf. (+45) 9614 9614 · Fax:(+45) 9752 4720 · E-mail: deif@deif.com
Factory
Commissio-
set
ning value
ON
15kW
5s
5kW
0030
00
0030
001s
001s
DESCRIPTION
ON/OFF. If a parallel run with
other generators is to take
place, this value must be ON.
Otherwise, the genset will not
take part of the load sharing
Lowest possible load of
generator for starting. Prevents
idle parallel running.
Delay before start based on start
point.
0...999 kW. Stop of running
generator point if available
power is increasing.
0...6900 kW. Available power
start point for next generator
when generators are running
parallel with mains operation.
0..8. Start priority of the genset
in question. 0 selects start
priority based on running hours,
other gives the actual priority no.
0...6900 kW. Available power
start point for next generator
when generators are running
parallel in island operation.
0...999s. Start delay timer, start
on available power low
condition.
0...999s. Stop delay timer