Deif MPC-1 Programming Manual page 22

Multi power controller
Table of Contents

Advertisement

Possible configurations: See next page.
The aux. relays can be chosen to give signal (close) according to the following
parameters:
01:
Fail type 1 (warning)
02:
Fail type 2 (soft stop)
03:
Fail type 3 (shutdown)
04:
Firing speed reached
05:
Mains fail
06:
Battery voltage
07:
Auto running mode ON
08:
Hand running mode ON
09:
Test running mode ON
10:
Stopped by operator
11:
Generator undervoltage
12:
Generator overvoltage
13:
Underspeed
14:
Overspeed
15:
Overcurrent
16:
Sync. Fail
17:
Start fail
18:
Asymmetric load
19:
Overload
20:
Reverse power
21:
Unit ready
22:
Limit, analog input 1
(P setpoint), warning
23:
Limit, analog input 2, warning
24:
Limit, analog input 3, warning
25:
Limit, analog input 4, warning
26:
Limit, analog input 5 (PTC),
warning
27:
Limit, analog input 6 (Pt100 1),
warning
The relays are capable to handle up to 3 messages in a logic manner, using the
following operators:
+ = OR
* = AND
Examples:
Functions
Page 22 of 35 Tlf. (+45) 9614 9614 · Fax:(+45) 9752 4720 · E-mail: deif@deif.com
28:
29:
30:
31:
32:
33:
34:
35:
36:
37:
38:
39:
40:
41:
42:
43:
44:
45:
46:
47:
48:
49:
50:
51:
55:
56:
57:
- = NOT
Description
Limit, analog input 7 (Pt100 2),
warning
Limit,
analog
input
setpoint), alarm
Limit, analog input 2, alarm
Limit, analog input 3, alarm
Limit, analog input 4, alarm
Limit, analog input 5 (PTC),
alarm
Limit, analog input 6 (Pt100 1),
alarm
Limit, analog input 7 (Pt100 2),
alarm
Digital input, term 34
Digital input, term 35
Digital input, term 36
Digital input, term 61
Digital input, term 62
Digital input, term 63
Digital input, term 64
Digital input, term 65
Digital input, term 66
Digital input, term 67
Digital input, term 68
Digital input, term 69
Digital input, term 70
Digital input, term 71
Digital input, term 72
Digital input, term 73
Common alarm
Common shutdown
Engine running
1
(P

Advertisement