Voltage Controller Analog Output (Option B2/B3); Constant Power Controller And External Setpoint - Deif MPC-1 Programming Manual

Multi power controller
Table of Contents

Advertisement

Volt. controller
Nz = 20 V
Volt. controller
Time pulse>080ms
Volt. controller
Gain Kp = 10.0
2.7.4

Voltage controller analog output (Option B2/B3)

DISPLAY
P-amplification
V Kpr
100
Delay time
V Tn
02.5s
2.7.5

Constant power controller and external setpoint

DISPLAY
Power controller
ON
Power controller
Ramp=010kW/s
Power limit
Pmax.= 120 %
01.0V
065ms
15.0
Factory
Commis-
set
sioning
value
100
02.5s
Factory
Commis-
set
sioning
value
010 kW/s
100%
Programming manual MPC-1
4...60 V (1...20 V) neutral zone.
(../110(100) V version: The voltage
refers to secondary side of voltage
transformer).
Island operation: Voltage within U
nom. ± neutral zone causes no
controller action.
Dynamic synchronisation: Max.
Differential voltage = neutral zone
value.
10...250 ms. Min. Impulse time for
controller relay outputs.
Min. time required for the ge-
nerator AVR to react on impulse.
1.0...99.9 amplification factor for
frequency controller.
The Kp affects the ON time for the
relay output. Kp ­ = ON time ­.
DESCRIPTION
0...500. P-band factor for controller
function
0...99s. I-time factor for controller
DESCRIPTION
ON/OFF. ON: In parallel with
mains, the generator will maintain
a constant power production.
5...100 kW/s. Ramp speed for
power controller.
10...120%. Power controller upper
limit value, referring to generator
nominal power. Upper limit, to pre-
vent overload, e.g when running
constant power from mains (peak
shaving, option F).