Temperature Inputs - Deif MPC-1 Programming Manual

Multi power controller
Table of Contents

Advertisement

4.4 Temperature inputs

DISPLAY
Analog input 5
ON
Name and
unit
Gen PTC
000%
Value at
0 %
0000
Value at
100%
0060
Limit warning
Value
= 1000
Limit shutdown
Value
= 1002
Delay
= 001s
Monitoring:
High limit mon.
Temperature 6
Pt100 ON
***name****
Pt 100 1 000 o C
Limit warning
= 092 o C
Limit shutdown
= 102 o C
Delay
= 001s
Monitoring:
High limit mon.
Factory
Commis-
set
sioning
value
ON
0000
0060
1000
1002
001s
High
001s
High
Programming manual MPC-1
DESCRIPTION
ON/OFF. Selection of temperature 1 input
ON/
OFF. PTC type 0...15 k .
Fixed value.
Zeropoint setpoint
Fullscale setpoint
0...9994. Limit for warning
0...9999 Limit for shutdown
0...999s. Delay for both warning and
shutdown.
high limit mon./low limit mon. Selection of
high or low limit monitoring.
0...255 o C.
0...255 o C.
0...999s. Delay for both warning and
shutdown.
high limit mon./low limit mon. Selection of
high or low limit monitoring.
4189340103E

Advertisement

Table of Contents