Dielsel/Gas Engine Selection; Start Sequence, Diesel Engine; Start Sequence, Gas Engine - Deif MPC-1 Programming Manual

Multi power controller
Table of Contents

Advertisement

6.2 Diesel/gas engine selection
DISPLAY
Facto-
ry
set
Start-stop-
Diesel
Logic
For
dieselengine

6.3 Start sequence, diesel engine

DISPLAY
Factory
Set
Preglow time
05s
05 s
Starter time
05s
03 s
Start pause
10s
time
10s
Gov. Down
OFF
bef.
Start
OFF
Start/stop
Running
logic
relay
Running
relay

6.4 Start sequence, gas engine

DISPLAY
Facto-
ry
Set
Ign. Delay
03s
0.5 s
Commis-
DESCRIPTION
sioning
value
Dieseleng/gasengine. Choice of start sequ-
ence for diesel or gas engine.
If "diesel" is chosen, the "running coil" (ter-
minal 43-44) will be activated during running
and the "preglow" (terminal 37-38) will be
activated before and during start.
If "gas" is chosen, the "ignition" (terminal 37-
38) and the "gas valve" (terminal 43-44) will
be activated after run out of delay timer (see
later).
Commis-
DESCRIPTION
sioning
vaue
0...99s. Preglow time before start (terminal
37-38). After timer runout, the start motor is
engaged until firing speed is reached.
Preglow continues until firing speed.
0...99 s. Start motor engagement time.
1...99 s. Delay between start attempts.
ON/OFF. If ON is chosen, a 4 sec. signal
"speed down" will be sent to governor,
before start is attempted.
Running Coil/Stop coil. Selection between
start/stop logic via running coil or stop coil.
Commis-
DESCRIPTION
sioning
value
0...99 s. Delay of ignition after engagement
of start motor.
Programming manual MPC-1
4189340103E

Advertisement

Table of Contents
loading