Emergency Power - Deif MPC-1 Programming Manual

Multi power controller
Table of Contents

Advertisement

G.break.blackout
Operation
ON
G.break.blackout
df max.= 0.25Hz
G.break.blackout
dU max. = 40V
m.break.blackout
operation
ON
Sync. Time contr.
ON
Mains trip
via GCB
Sync time contr.
ON
Sync. Time contr.
Delay time
180s
2.7.9

Emergency power

DISPLAY
Config. emer.
Power?
YES
Emer.power
ON
Emergency power
start delay
15s
Main
Delay time
15s
Emergency power
stop delay
10s
ON
0.25hz
40V
ON
ON
GCB
ON
120s
Factory
Commis-
set
sioning va-
lue
YES
ON
03s
03s
20s
Programming manual MPC-1
ON/OFF. Selects generator
breaker blackout start active
when ON
0.05...0.49Hz Blackout start
frequency deviation.
2...60 V. Blackout start
undervoltage
ON/OFF. Blackout start, mains
breaker (option A).
ON/OFF. Supervision of syn-
chronisation time of breakers
GCB/MCB. Choice of trip of gen.
breaker (GCB) or mains breaker
(MCB) if a mains failure occurs.
ON/OFF. Choise of
synchronisation time supervision
0...999s. Set-point of synchroni-
sation timer. At runout, alarm
"Sync. Time" and horn output is
released.
DESCRIPTION
YES/NO. If NO is chosen, the
following sub-menus will not be
shown.
ON/OFF. ON: Upon mains fail, the
genset is started and used as
emergency power source.
0...99s. Start delay after mains
failure occurs.
0...99s. Delay after mains
restoration before re-
synchronising.
0...99s. Stop delay after mains
restored. Emergency power supply
running time after return of the
mains.
4189340103E