Quick Start Procedure
STEP
Application Specifi c Setup
7
7.1
Confi gure the iQpump Micro for a dedicated pump application. DO NOT RUN
THE MOTOR. Ensure all protective covers are installed and power is turned on.
Available iQpump Micro Application Macro Settings using parameter A1-03 :
• 6008 Constant Pressure Mode (PSI) [Factory Default] Note: Do not change unless pump application differs from default.
• 6009 Pump Down Level Mode (Ft)
• 7770 General Purpose Mode
• 7771 Submersible Motor GP Mode
7.2 Select Application Macro Parameter A1-03
Hold
button for 3 sec. to go back to the main menu.
YASKAWA TOEP YAIQPM 01A iQpump Micro Quick Start Procedure
LED Digital Operator (Standard)
Press
two times until the digital operator shows the parameter menu.
5 00. 0
2X
A1-03
0000
Inc./Dec. Selection
Switch to Edit Mode
Enter Application Parameters (Standard)
Hold
button for 3 sec. to go back to the main menu.
5 00. 0
5tuP
3X
1. 9 0
2. 9 0
Switch to Edit Mode
Modify Value
Go Back to Main Menu (Standard)
PAr
A1-01
2X
6008
Select Application
Press
E2-01
Select Parameter.
E2-01
Save New Value
to select.
Page 20
of 31