YASKAWA iQpump Micro Quick Start Manual page 25

Ac drive compact intelligent pump controller quick start procedure
Hide thumbs Also See for iQpump Micro:
Table of Contents

Advertisement

iQpump Micro
Quick Start Procedure
STEP
Fine-tune Settings for Pumping Application (continued)
10
10.3
SLEEP MODE (Example)
60 Hz
Output Frequency
(pump motor speed)
0
10.4
PUMP SYSTEM FAULT SETUP
The iQpump Micro can display a 'Setpoint Not Met' fault when the iQpump Micro is unable to maintain the
programmed system setpoint due a problem with the pump system. Set P1-15 to the maximum allowed difference
between setpoint and feedback level.
SETPOINT
10.5
LOW/HIGH FEEDBACK LEVEL DETECTION
The iQpump Micro continuously monitors the system feedback signal. Set the low feedback level parameter P1-08
to the minimum feedback level allowed for your system to display a 'Low Feedback' fault. Set the high feedback
level parameter P1-11 to the maximum feedback level allowed to display a 'High Feedback' fault.
10.6
PRE-CHARGE OPERATION
This function is used when the pump system requires a pre-charge before normal operation. Upon start the iQpump
Micro will run at a fixed speed for a specified time or until the feedback signal reaches a programmed level after
which it will switch to auto mode operation.
Pre-Charge Lvl. P4-01
Pre-Charge Freq. P4-02
10.7
THRUST BEARING - SUBMERSIBLE MOTORS
The factory recommends using the Thrust Bearing
function to prevent excess motor wear when using
a submersible motor in combination with the
iQpump Micro. Enter the minimum motor
frequency in parameter P4-11 to enable this
function. Example: Minimum motor speed 1800
RPM, 1800 RPM ÷ 3600 RPM x 60.0 Hz = 30.0 Hz
Thrust Acceleration Time P4-11
(Example 1.0 sec.)
Thrust Bearing Frequency P4-12
(Example 30.0 Hz)
10.8
AUTO OPERATION - POWER DOWN STORAGE
Allows the iQpump Micro to automatically start after power failure when operated from the digital operator. This
function is recommended when operating the iQpump Micro in remote/unmanned areas.
Use parameter P4-10 to enable this function.
WARNING! Stay Clear- Equipment starts automatically. An internal run command will
automatically occur on power-up if the iQpump Micro is powered down while running.
Sleep Delay Time (P2-03)
(Example 5.0 sec.)
Pump Running
Go to Sleep
Time
FEEDBACK SIGNAL
Setpoint-LOP Tim
Time
Output
Frequency
0 Hz
P4-01 Pre-Charge Level: Specified feedback level to stop pre-charge operation
P4-02 Pre-Charge Frequency: Set desired pre-charge speed
P4-03 Pre-Charge Time: Specified maximum pre-charge operation time
DEFAULT SETTING
SYSTEM GOES TO SLEEP WHEN PUMP
MOTOR SPEED DROPS TO 40 Hz
(2400 RPM for 3600 RPM Motor).
Minimum Speed P1-06
(Example 40.0 Hz)
Ramp or Coast to Stop, b1-02
WAIT FOR PRESSURE TO FALL BELOW START /
DRAW DOWN LEVEL (P1-04)
P1-15 Max Setpoint Diff
P1-16
SET-POINT NOT MET
Pre-Charge Completed
Auto Operation
Turn Off Thrust Bearing Function
(Thrust Frequency Reached)
C1-01 Acceleration Time
Output Frequency
Time
Thrust
Auto/Hand Operation
Bearing
YASKAWA TOEP YAIQPM 01A iQpump Micro Quick Start Procedure
Feedback
Page 25
of 31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents