iQpump Micro
Quick Start Procedure
STEP
Install the 24 V Transducer Power Supply (continued)
5
5.21
Connect transducer wiring to the 24V Power Supply terminals using
D
A
24V
AC
A2
C
A – Terminal block CN1
B – Avoid fraying wire strands when
stripping insulation from wire. Strip
length 5.5 mm.
C – Single wire or stranded wire
NOTICE: Separate transducer wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1, V/T2, W/T3,
⊕ 2) and other high-power lines. Improper wiring practices could result in drive malfunction due to electrical interference.
NOTICE: Damage to Equipment. Do not tighten screws beyond the specified tightening torque. Failure to comply may damage
the terminal block.
CN1 Terminal Block
24V
AC
A2
YASKAWA TOEP YAIQPM 01A iQpump Micro Quick Start Procedure
Preparing Wire
E
Terminal Ends
B
FE
Figure 1.10 24V Power Supply Wiring Guide
Refer to 24V Power Supply Wire Size and Torque Specifications on page 13
Table 1.17 24V Power Supply Terminal Block CN1
Terminal No.
24V
AC
FE
A2
FE
Figure 1.10
C1
C2
24V AC A2 FE
D – Loosen screw to insert wire.
E – Blade depth of 0.4 mm or less
Blade width of 2.5 mm or less
Terminal Name (Function)
Tranducer Power Supply
Power Supply Common
Analog input
Functional Earth Ground for
Shielded Connection
as a guide.
Transducer Wiring
(Customer Supplied)
Strain Relief
Shielded
Transducer Cable
⊖ , ⊕ 1,
for details.
Function (Signal Level)
Default Setting
+20V to +24V Vdc 30 mA
0 Vdc
4-20 mA, 0-20 mA, 0-10 Vdc
Page 16
of 31