Install the 24 V Transducer Power Supply (continued)
5
5.24
On IP66/NEMA 4X, UL Type 4X models, insert the digital operator cable from the front cover into port CN1 on the
drive.
IP20/NEMA 1, UL Type 1
Not applicable.
5.25
To complete the installation procedure on IP66/NEMA 4X, UL Type 4X enclosures, reattach the front cover of the
drive enclosure. Refer to
NOTICE: Damage to Equipment. Take proper precautions when wiring the 24V Power Supply unit so that the front covers will
easily fit back onto the drive. Make sure no cables are pinched between the front covers and the drive when replacing the cover.
Failure to comply may result in damage to circuitry and equipment.
IP20/NEMA 1, UL Type 1
Not applicable.
Table 1.22 IP66/NEMA 4X, UL Type 4X Enclosure Front Cover Installation Bolt Size and Tightening Torque
Voltage Class
Single-Phase 200 V Class
Three-Phase 200 V Class
Three-Phase 400 V Class
YASKAWA TOEP YAIQPM 01A iQpump Micro Quick Start Procedure
Table 1.20 Insert Digital Operator Cable
Table 1.22
for tightening torque specifications.
Table 1.21 Attach Enclosure Front Cover
Drive
Drive Model
BV0001G to BV0012G
2V0001G to 2V0020G
2V0030G to 2V0069G
4V0001G to 4V0011G
4V0018G to 4V0038G
IP66/NEMA 4X, UL Type 4X
CN1 Port
Drive
IP66/NEMA 4X, UL Type 4X
Installation Screw Size
M5
M5
M6
M5
M6
Insert Digital
Operator Cable
Inside Front Cover
Front Cover Screw (4)
Front Cover
Tightening Torque N m (lb-in)
2.0 to 2.5 (17.7 to 22.1)
2.0 to 2.5 (17.7 to 22.1)
5.4 to 6.0 (47.8 to 53)
2.0 to 2.5 (17.7 to 22.1)
5.4 to 6.0 (47.8 to 53)