Perform Mechanical Installation
3
3.1 Verify installation environment.
Mechanical installation and mounting footprint vary by model. Refer to the iQpump Micro User Manual No. TOEP YAIQPM 03 ,
Chapter 2: Mechanical Installation for details. Ensure the installation conditions are suitable to prolong and optimize performance
life.
Environment
Conditions
Installation Area
Indoors
Ambient Temperature
-10 to + 40 °C (+14 to +104 °F) NEMA 1, UL Type 1 Enclosure
Humidity
95% RH or less and free of condensation
Storage Temperature
-20 °C to +60 °C (-4 °F to +104 °F)
Surrounding Area
Install the drive in an area free from:
Altitude
Up to 1000 meters without derating. Up to 3000 meters with output current and voltage derating
Orientation
Install the unit vertically to maintain maximum cooling effects.
3.2 Maintain installation clearances.
Single Drive Installation
Side Clearance
A
Multiple Drive Installation
B
A
2 mm
Install Type
Single drive
Multiple drive
installation
oil mist and dust
metal shavings, oil, water, or other foreign materials
radioactive materials
combustible materials (e.g., wood)
harmful gases and liquids
excessive vibration
chlorides
direct sunlight.
Top/Bottom Clearance
A
C
C
B
C
C
Minimum Spacing
A
• Airfl ow
30 mm (1.18 in)
Align the tops of
30 mm (1.18 in)
the units
Ensure the back panel is placed against a closed fl at
surface for proper cooling.
NOTICE: Abnormal Operation. Avoid placing peripheral
B
devices, transformers, or other electronics near the
bypass as the noise created can lead to abnormal
operation. Take proper steps to shield the bypass from
electrical interference if such devices must be used in
close proximity to the Bypass.
NOTICE: Equipment Damage. Prevent foreign matter
such as metal shavings and wire clippings from falling
into the bypass during installation. Failure to comply could
result in damage to the bypass. Place a temporary cover
over the top of the drive during installation. Remove the
temporary cover before bypass start-up, as the cover will
D
reduce ventilation and cause the bypass to overheat.
B
C
100 mm (3.93 in)
direction
100 mm (3.93 in)
D
-
Airfl ow direction
YASKAWA TOEP YAIQPM 01A iQpump Micro Quick Start Procedure