2.6 Parameter settings for the heating engineer

Configuration and parameter settings to be made by the heating engineer.
Buttons
Explanation
1
Press both line selection buttons for at least 3 seconds.
This will take you to the programming level "Enduser".
2
Press the line selection buttons to select the required
line.
The parameter list on the next two pages contains all
lines on which settings can be made.
3
Press the + or - button to set the required value.
The setting will be stored as soon as you leave the
programming mode or change to another line.
4
You leave the programming level "Heating engineer" by
pressing one of the operating mode buttons.
 Note:
If no button is pressed for about 8 minutes, the con-
troller will automatically return to the operating mode
selected last.