4.156 Operating action of the return diversion
(ZuFu1)
Defines if auxiliary function "Return diversion" (ZuFu1) is used for raising or lowering
the return temperature.
Setting range
1...2
Entry:
1
Return diversion is used for lowering the return temperature
2
Return diversion is used for raising the return temperature
For a description of the auxiliary function, refer to operating lines 140 and 141.
The temperature differentials required for activating the function can be set on operat-
ing lines 480 and 481.
4.157 Storage tank sensor for the return diversion
(ZuFu1)
Defines which of the buffer storage tank sensors shall use auxiliary function "Return di-
version" (ZuFu1) for generating the temperature differentials (operating lines 480 and
481).
Setting range
1...3
The temperature differential acquired is that between return sensor B73 and one of the
following selected sensors:
1
Buffer storage tank sensor B4
2
Buffer storage tank sensor B41
3
Buffer storage tank sensor B42
To ensure proper functioning, the sensors must be correctly located.
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings