5.29 P-band minimum limitation of the return
temperature of the wood-fired boiler (Xp)
• Adapting the control characteristic to the plant's behavior (controlled system).
• P-band of the PI controller can be adjusted
Setting the proportional band for the control of the mixing valve actuator used for the
maintained boiler return temperature.
Setting range
1...100
The proportional band defines within which change of the control variable
return) the whole correcting span y (valve travel) is traversed.
The smaller the proportional band, the greater the change of the manipulated variable
Δ
y at a given change of the control variable
y
Tn
x
5.30 Integral action time minimum limitation of the
return temperature of the wood-fired boiler
(Tn)
• Adapting the control characteristic to the plant's behavior (controlled system)
• I-part of the controller can be adjusted
Setting the integral action time for the control of the mixing valve actuator used for the
maintained boiler return temperature.
Setting range
10...873
The integral action time is the period of time the controller's I-part would require to pro-
duce the same change of the manipulated variable as the P-part
An adjustment of the integral action time changes the valve's rate of response.
The longer the integral action time Tn, the slower the response of the controlled sys-
tem.
For graph, refer to operating line 381
Basic Documentation RVP540 / RVP550
Description of the EXP settings
Unit
K
Δ
x.
1
Xp
t
t
Unit
s
.
EXP
Factory setting
24
Δ
x (
Δ
T of the
Factory setting
90
CE1P2488en
18.10.2002

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sigmagyr rvp550

Table of Contents