Advertisement

Boiler boost
 Note
Benefit
Note
Setting
Effect
Correction
 Note
Siemens Building Technologies
HVAC Products
The controller generates the boiler temperature setpoint based on the boost set here
and the current flow temperature setpoint:
The greater the temperature differential between boiler flow and mixing heating circuit,
the quicker the required setpoint can be reached.
TVw
Setting 702
EXP
Total
Also refer to "heating curve slope" in Index.

5.49 Gain factor of room influence (KORR)

• The influence of room temperature deviations on the controlled system can be ad-
justed
Defines the influence of room temperature setpoint deviations on the controlled system.
The room influence can be activated and deactivated (operating line 721).
Setting range
0...20
Changing this setting has the following impact:
Entry:
Increase:
Authority of room influence will increase
Decrease:
Authority of room influence will decrease
The value of setting 701
EXP
perature setpoint minus actual room temperature).
The result is then added to the room temperature setpoint.
TRwk
=
TRw
TRw Room temperature setpoint
TRx
Actual value of the room temperature
TRwk Corrected room temperature setpoint
The gain factor of the room influence is only active when a room unit is connected.
Basic Documentation RVP540 / RVP550
Description of the EXP settings
Flow temperature setpoint
Boost
Boiler temperature setpoint
Unit
is divided by 2 and multiplied by the differential (room tem-
701
OEM
+
(TRw
-
TRx)
2
Factory setting
4
p
309/348
CE1P2488en
18.10.2002