Values; Nominal D.h.w. Temperature Setpoint - Siemens SIGMAGYR RVP540 Basic Documentation

Heat energy manager
Hide thumbs Also See for SIGMAGYR RVP540:
Table of Contents

Advertisement

Benefit
Setting
Effect
D.h.w. temperature
setpoints
D.h.w. charging
Note
Siemens Building Technologies
HVAC Products
D.h.w. values

3.16 Nominal d.h.w. temperature setpoint

• D.h.w. is heated only if there is demand for it.
• Possibility of using 2 different d.h.w. temperature setpoints
Setting range
TBWR...TBWmax
TBWR
Reduced setpoint of the d.h.w. temperature (setting on operating line 770)
TBWmax
Maximum nominal setpoint of the d.h.w. temperature (setting on operating line 750
The temperature setpoint during normal d.h.w. operation will be changed.
0
10
20
30
26
Setting "Nominal d.h.w. temperature setpoint"
770
Setting "Reduced d.h.w. temperature setpoint"
750
Setting "Maximum nominal setpoint of the d.h.w. temperature"
EXP
D.h.w. heating has 2 different setpoints that can be used:
• Nominal d.h.w. temperature setpoint: It ensures the d.h.w. temperature required
during main occupancy times
• Reduced d.h.w. temperature setpoint (setting on operating line 770): it ensures the
d.h.w. temperature required during the main occupancy times.
The criteria required for releasing d.h.w. heating are defined by the settings made on
operating lines 771, 773 and 774.
In the event of a sensor with an open-circuit, the d.h.w. will not be heated (risk of
scalding).
Basic Documentation RVP540 / RVP550
Description of the enduser settings
Unit
°C
40
50
60
70
80
Factory setting
55
)
EXP
90
100
120
130
140
CE1P2488en
18.10.2002
°C
69/348

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sigmagyr rvp550

Table of Contents