Siemens SIGMAGYR RVP540 Basic Documentation page 213

Heat energy manager
Hide thumbs Also See for SIGMAGYR RVP540:
Table of Contents

Advertisement

Bivalent-parallel
 Note
Benefit
Description
Setting
Effect
Examples
Siemens Building Technologies
HVAC Products
So that the heat sources are always released, setting "---" must be selected on the re-
spective operating lines (standard setting).
OeG
Wp
30
20
10
Bivalent-parallel and bivalent-partially-parallel operation is not possible with partial dia-
grams OeG9, Wp5 and Ho5.
4.190 Release of oil- / gas-fired boiler below the
outside temperature threshold
• The outside temperature for release of the oil- / gas-fired boiler can be defined
Definition of the outside temperature below which the oil- / gas-fired boiler may be put
into operation.
Setting range
--- / -30...30
---
Oil- / gas-fired boiler is always released
The oil- / gas-fired boiler is released when the composite outside temperature lies be-
low the adjusted value. If the outside temperature lies above the adjusted value, the oil-
/ gas-fired boiler is locked.
The switching points for release and locking are separated by a switching differential to
absorb small outside temperature variations.
Refer to "Release of outside temperature" (before operating line 630).
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
0
-10
-20
Unit
°C
-30
°C
TAx
ged
Factory setting
- - -
213/348
CE1P2488en
18.10.2002