Siemens RVP201 Basic Documentation

Siemens RVP201 Basic Documentation

Heating controllers
Table of Contents

Advertisement

Heating Controllers
RVP201 and RVP211
Basic Documentation
Edition 2.0
Controller series A
CE1P2464en
Building Technologies
2017-07-21

Advertisement

Table of Contents
loading

Summary of Contents for Siemens RVP201

  • Page 1 Heating Controllers RVP201 and RVP211 Basic Documentation Edition 2.0 Controller series A CE1P2464en Building Technologies 2017-07-21...
  • Page 2 Siemens Switzerland Ltd Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 58-724 24 24 Fax +41 41-724 35 22 © 2007 Siemens Switzerland Ltd www.siemens.com/sbt Subject to change 2/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 2017-07-21...
  • Page 3: Table Of Contents

    Field of use with regard to heating systems ............ 9 Field of use with regard to functions ..............9 Application examples ..................10 2.5.1 Flow temperature control with RVP201 ............10 2.5.2 Boiler temperature control with RVP201 ............10 2.5.3 Boiler temperature control with RVP211, d.h.w.
  • Page 4 Low voltage side .................... 35 5.1.2 Mains voltage side ..................35 5.1.3 Auxiliary terminals ..................35 Connection diagrams ..................36 5.2.1 Low voltage side .................... 36 5.2.2 Mains voltage side ..................37 4/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464D Building Technologies Contents 2017-07-21...
  • Page 5 6.1.2 Dimensions ....................38 6.1.3 Outside view ....................39 Time switches ....................39 6.2.1 General ......................39 6.2.2 Analog time switches AUZ3… ............... 39 Technical data ....................41 5/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies Contents 2017-07-21...
  • Page 6 6/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464D Building Technologies Contents 2017-07-21...
  • Page 7: Brief Description And Features

    Summary Brief description and features RVP201 and RVP211 are heating controllers designed for use in smaller plants. The only difference between the two types of controllers is the d.h.w. heating function: RVP201: without d.h.w. heating RVP211: with d.h.w. heating The RVP201/211 controller is designed for use in smaller residential and non- residential buildings that have their own heat generating plant The RVP201/211 is a flow temperature controller.
  • Page 8: Suitable Room Units

    Room unit QAA50.. Room unit QAW70 1.3.3 Suitable actuators For three-position control, electric or electro-hydraulic actuators from Siemens with the following features can be used: Operating voltage AC 24…230 V Maximum running time 6 minutes (ideally 2 to 3 minutes)
  • Page 9: Use

    Field of use with regard to types of buildings The RVP201/211 is basically suited for all types of buildings that use weather- or room temperature-compensated heating control systems. The controllers are however de-...
  • Page 10: Application Examples

    Application examples 2.5.1 Flow temperature control with RVP201 Three-position con- trol, acting on mixing valve 2.5.2 Boiler temperature control with RVP201 Two-position control, acting on burner 2.5.3 Boiler temperature control with RVP211, d.h.w. heating with charging pump Two-position control, acting on burner, d.h.w.
  • Page 11: Flow Temperature Control With Rvp211

    Outside sensor Heat generating equipment (boiler) Load (room) D.h.w. storage tank Heating circuit pump D.h.w. charging pump Controller RVP201/211 Motorized three- or two-position mixing valve Motorized changeover valve 11/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 2 Use 2017-07-21...
  • Page 12: Technical Design

    Heating circuit pump runs Control with seat or slipper valve: relay de-energized Control with burner: boiler always ON D.h.w. charging pump runs or d.h.w. changeover valve is deactivated The RVP201 does not provide “d.h.w. heating only”. 12/46 Siemens Heating controllers RVP201 and RVP211...
  • Page 13: Acquisition Of Actual Values

    In the case of serious faults that do not allow the RVP201/211 to ensure control, a fault message will be generated. This is indicated on the controller front by the LED which starts flashing when the current operating mode is overridden.
  • Page 14: Temperature

    "6 Mechanical design". 3.3.3 Compensating variables Outside temperature The RVP201/211 differentiates between three types of outside temperatures: The actual outside temperature (T The attenuated outside temperature (T ). It is generated by filtering the actual out- side temperature by the building time constant. This means that compared to the ac- tual outside temperature, the attenuated outside temperature is significantly damp- ened, thereby representing the long-term development of the outside temperature.
  • Page 15 In the case of short-time variations of the outside temperature, the composite outside temperature (T ) prevents the control from responding too quickly. With weather-compensated control, the RVP201/211 only uses the composite outside temperature. (B9) Generation of composite and attenuated outside temperature...
  • Page 16: Heating Curve Chart

    The heating curve slope is set with a setting knob on the front of the controller. 16/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design 2017-07-21...
  • Page 17 The basic setting is to be made in agreement with the planning documentation or ac- cording to local practices. The heating curve is based on a room temperature setpoint of 20 °C. 17/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design 2017-07-21...
  • Page 18: Generation Of Setpoint

    The generation of this factor corresponds exactly to the generation of the flow temperature setpoint in the case of weather-compensated control with or without room temperature influence. 18/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design 2017-07-21...
  • Page 19: Control

    / actual value deviation of the room temperature the selected heating curve slope The purpose of room influence is to enable the controller to exactly reach and maintain the respective setpoint. 19/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design 2017-07-21...
  • Page 20: Control Process

    / off mode until the setpoint is reached. The switching differential is constant at 1 K (fixed value). The RVP201/211 is suited to drive electro-thermal actuators with a running time of 8 to 16 minutes.
  • Page 21: Limitations

    The burner's switch-off point cannot be higher than the maximum limit value. In that boiler temperature case, the switch-on point will be lower by the amount of the set switching differential. This function can be disabled. 21/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design 2017-07-21...
  • Page 22: Optimization Functions

    Quick setback can be provided only if a room temperature sensor (room unit) is used. This function can be deactivated with the setting potentiometer E (position Off). 22/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design...
  • Page 23: Eco Automatic Energy Saver

    (mixing valve closes or burner off, heating circuit pump off). In the RVP201/211, the ECO automatic energy saver is subdivided into two part func- tions. ECO function 1 is used predominantly in the summer while ECO function 2 re- sponds primarily to short-term temperature variations and is therefore active during intermediate seasons.
  • Page 24: Heating Limit

    (mains voltage present). Frost protection for the plant can be provided with or without an outside sensor. The switching differential is 1 K (fixed value). 24/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design 2017-07-21...
  • Page 25: Frost Protection For The Building

    (Q3) for the control of the d.h.w. charging pump or the d.h.w. changeover valve a setting facility for the d.h.w. temperature setpoint a setting facility for the priority 25/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design 2017-07-21...
  • Page 26: Acquisition Of D.h.w. Temperature

    In manual operation, d.h.w. heating is switched on; the charging pump is enabled. With d.h.w. heating (charging pump or changeover valve), the switching differential lies Switching differential asymmetrically below the setpoint: 26/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design 2017-07-21...
  • Page 27 SD = 5 K Switching differential Time D.h.w. temperature Setpoint of d.h.w. temperature Actual value of d.h.w. temperature 27/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design 2017-07-21...
  • Page 28: Heating With Changeover Valve

    The factory-set pump overrun time is 6 minutes. Depending on the type of plant and the operational status, overrun of the heating circuit pump and the charging pump acts as follows: 28/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 3 Technical design 2017-07-21...
  • Page 29: Pump Kick

    Interactions with room units 3.9.1 General Room units can act on the RVP201/211 only if the controller works in one of the two automatic modes The room temperature acquired by a room unit is adopted by the RVP201/211 at terminal A6. If the room temperature acquired by the room unit shall not be consid- ered by the control functions, the room authority must be set to 0 %.
  • Page 30: Interactions With Room Unit Qaa50

    To enable the QAA50.. to act on the controller, the latter must meet the following oper- ating conditions: Automatic mode A6–MD not bridged (that is, external changeover switch, if present, must be open) The actions of the QAA50.. operating mode slider on the RVP201/211 are as follows: Operating mode Operating mode RVP201/211 QAA50..
  • Page 31 To enable the QAW70 to act on the controller, the latter must meet the following operat- ing conditions: Automatic mode A6–MD not bridged (that is, external changeover switch, if present, must be open) The actions of the QAW70 operating mode buttons on the RVP201/211 are as follows: Operating mode Operating mode RVP201/211 QAW70 Automatic mode ;...
  • Page 32 Operating Function, parameter Effect on RVP201/211, notes line Second heating period, Overrides the time switch of the RVP201/211 start of reduced heating Third heating period, Overrides the time switch of the RVP201/211 start of normal heating Third heating period, Overrides the time switch of the RVP201/211 start of reduced heating Entry weekday 1…7...
  • Page 33: Handling

    Operating elements Operating elements for the user Slider for selecting the operating mode (the RVP201 does not have the position LED (lit when operating mode is overridden; flashes when a fault is present) Time switch Setting knob for slope of heating curve Setting knob for setback to the reduced temperature Setting knob for the d.h.w.
  • Page 34: Setting And Readjusting The Room Temperature

    For manual readjustment of the room temperature, use setting knob ; its scale gives the room temperature differential in °C; this setting produces a parallel dis- placement of the heating curve 34/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 4 Handling 2017-07-21...
  • Page 35: Selection Of Operating Mode

    4.2.2 Mounting methods The RVP201/211 is designed for three different mounting methods: Wall mounting: the base is secured to a flat wall with the help of three fixing screws Rail mounting: the base is fitted to the top hat rail Flush panel mounting: the base is fitted in a panel cutout measuring 138 ×...
  • Page 36: Engineering

    Q3/Y3 D.h.w. charging pump or changeover valve ON 5.1.3 Auxiliary terminals In addition to the standard connection terminals, the base accommodates three auxiliary terminals: M; N and 36/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 5 Engineering 2017-07-21...
  • Page 37: Connection Diagrams

    Flow or boiler temperature sensor D.h.w. temperature sensor (with RVP211 only) Outside sensor D.h.w. thermostat (only with RVP211) Controller RVP201/211 External switch for changeover of operating mode 37/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 5 Engineering 2017-07-21...
  • Page 38: Mains Voltage Side

    Manual reset safety limit thermostat Heating circuit pump D.h.w. charging pump (only with RVP211) Controller RVP201/211 Three-position actuator Two-position actuator Actuator for d.h.w. changeover valve (only with RVP211) 38/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 5 Engineering 2017-07-21...
  • Page 39: Mechanical Design

    If the controller is used without a time switch (RVP201.0 or RVP211.0), the space for the time switch is covered up with a hinged cover. If a time switch is fitted at a later time, the appropriate hole in the cover must be cut out with a knife.
  • Page 40: Outside View

    6.2.1 General The RVP201/211 has an opening for fitting a plug-in type time switch. If desired, the time switch fitted can be replaced by another type (refer to "1.2 Type summary"). The time switch is simply plugged in. The electrical connections to the con- troller are established via a terminal strip so that no wiring is required.
  • Page 41 The resolution is thus one hour. However, since – for mechanical reasons – at least two tappets need to be tilted together to set one heating period, the shortest possible heat- ing period is two hours. 41/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 6 Mechanical design 2017-07-21...
  • Page 42: Technical Data

    (Applications) CE1T2464en_C1 *) EU conformity (CE) Eurasia conformity EAC conformity *) The documents can be downloaded from http://siemens.com/bt/download. Safety class II to EN 60730 Protective data Degree of protection (cover closed) IP40 to EN 60529 Degree of contamination 2 to EN 60730 Refer to ”Dimensions“...
  • Page 43 <95 % r.h. <95 % r.h. (non-condensing) (non-condensing) Mechanical conditions class 3M2 class 2M2 class 1M2 Use above sea level Max. 3000 m above sea level 43/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 7 Technical data 2017-07-21...
  • Page 44 ............20 mounting methods ............ 35 electric or electro-hydraulic actuators ......20 electro-thermal actuators ...........20 normal mode ............. 12 enabling of d.h.w. heating .........26 environmental conditions ...........43 44/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies 7 Technical data 2017-07-21...
  • Page 45 ........... 35 resolution ..............41 weather-compensated control with room influence ... 20 room authority ............19 weekly time switch AUZ3.7 ........41 room temperature ............. 13 45/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies Index 2017-07-21...
  • Page 46 Building Technologies Group International Headquarters Gubelstrasse 22 CH-6301 Zug Tel. +41 41 724 24 24 Fax +41 58 724 35 22 © 2007 Siemens Switzerland Ltd www.siemens.com/sbt Subject to change 46/46 Siemens Heating controllers RVP201 and RVP211 CE1P2464en Building Technologies Index 2017-07-21...

This manual is also suitable for:

Rvp211Rvp201.0Rvp211.0

Table of Contents