4.240 Circulating pump operation during the
legionella function
Flushing the circulation piping ensures that the legionella bacteria will also be killed in
that part of the plant.
Setting range
0 / 1
0
The circulating pump (ZuFu4, operating line 147) does not run during the time
the legionella function is performed.
1
The circulating pump (ZuFu4, operating line 147) runs during the time the le-
gionella function is performed.
If this function is deactivated, there is a risk that legionella bacteria will return from the
circulation piping to the d.h.w. storage tank right after the storage tank has been ther-
mally disinfected.
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
°C
Factory setting
1
CE1P2488en
18.10.2002