Temperature Differential Swimming Pool Off; Maximum Swimming Pool Charging Temperature; Heat Exchanger Pump Operation For Swimming Pool - Siemens SIGMAGYR RVP540 Basic Documentation

Heat energy manager
Hide thumbs Also See for SIGMAGYR RVP540:
Table of Contents

Advertisement

Description
Setting
Effect
Benefit
Description
Setting
Effect
Benefit
Description
Setting
Effect
148/348
Siemens Building Technologies
HVAC Products

4.82 Temperature differential swimming pool OFF

Swimming pool heating will be stopped when the temperature differential between col-
lector (B6 / B61) and swimming pool (B13) is too small.
Setting range
0... Line 319
As soon as the temperature differential is smaller than the value adjusted on this oper-
ating line, swimming pool heating will be stopped.
4.83 Maximum swimming pool charging
temperature
• Maximum limitation of the water temperature in the swimming pool
The swimming pool temperature adjusted here is the maximum to which the water is
heated.
Setting range
20...95
Charging will be stopped as soon as the maximum swimming pool charging tempera-
ture is reached.
Any surplus energy from the solar collectors will be delivered to the buffer / d.h.w. stor-
age tank until their safety temperature is reached and overtemperature protection de-
vices, if fitted, will respond.
4.84 Heat exchanger pump operation for
swimming pool
• Optional alternative or parallel operation of storage tank and swimming pool heating
You can choose whether the swimming pool shall be heated at the same time as the
storage tanks or afterwards.
Setting range
1 / 2
The temperature differentials on operating lines 329 through 332 serve as the switch-on
/ off criteria for the storage tanks, and the temperature differentials on operating lines
319 and 320 for the swimming pool.
The setting on this operating line has the following effect:
1
Alternatively
The energy from the solar collectors is delivered either to one of the storage tanks
or to the swimming pool.
Which of the storage tanks is charged first depends on the priority selected on op-
erating line 333.
Basic Documentation RVP540 / RVP550
Description of the heating engineer settings
Unit
Factory setting
K
4
Unit
Factory setting
°C
35
Unit
Factory setting
1
CE1P2488en
18.10.2002

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sigmagyr rvp550

Table of Contents