Second Heat Pump Stage; Locking Time Of Heat Pump Stage 2; Release Integral Heat Pump Stage 2 - Siemens SIGMAGYR RVP540 Basic Documentation

Heat energy manager
Hide thumbs Also See for SIGMAGYR RVP540:
Table of Contents

Advertisement

Example
Benefit
Description
Setting
Effect
Benefit
Description
Setting
Effect
Siemens Building Technologies
HVAC Products
T
1
WP
0
400
Display of the heat pump flow temperature setpoint
401
Actual value of the heat pump flow temperature B21
402
Display of the heat pump return temperature setpoint
403
Actual value of the heat pump return temperature B71
421
Heat pump switching differential ON
422
Heat pump switching differential OFF
413
Minimum compressor on time
EXP
414
Minimum compressor off time
EXP
416
Compensation of running time-related surplus heat
EXP

Second heat pump stage

5.40 Locking time of heat pump stage 2

• Prevents premature switching on of the second heat pump stage
The second heat pump stage may be released only when the locking time has elapsed.
The locking time starts at the point in time heat pump stage 1 is released.
Setting range
1..60
The locking time enables heat pump stage 1 to reach a stable condition before heat
pump stage 2 is allowed to switch on.

5.41 Release integral heat pump stage 2

• Prevents frequent switching on / off of heat pump stage 2
If the capacity of heat pump stage 1 is no longer sufficient, the controller starts calcu-
lating the heat deficit. For that, the controller calculates the temperature crossing below
the limit over time until the adjusted value is reached.
Setting range
0...500
As soon as the locking time for the second heat pump stage (operating line 420
elapsed, the controller starts calculating the heat deficit, if there is any.
When the integral is reached, heat pump stage 2 will be released.
Basic Documentation RVP540 / RVP550
Description of the EXP settings
Unit
Factory setting
min
10
Unit
Factory setting
K*min
50
t
) has
EXP
305/348
CE1P2488en
18.10.2002