Monitoring Control; Prompt; Con - Configuration Reports; Error - Error Codes - Lutron Electronics RadioTouch RTA-RS232 Setup And Installation Manual

Hide thumbs Also See for RadioTouch RTA-RS232:
Table of Contents

Advertisement

Monitoring Control

RTA-RS232 Responses

Prompt

This response from the RTA-RS232 informs the Host that the RTA-RS232 is ready to accept another command.
Once the Host issues a command, it must wait for a prompt before another command may be sent.
!<CR>
CON – Configuration Reports

The configuration reports inform the host of the current configuration settings.

~CON,RPT,[Category],{Zone Number}, [Data]<CR>
Category
Zone Number
TYPE
0 – 9
HAND
RB
ACK
REV
#.#
Examples:
~CON,RPT,TYPE,2,L <CR> Indicates that Zone #2 is configured as Lights.
~CON,RPT,RB,ON <CR> Indicates that Reply Back Mode is on
~CON,RPT,REV,3.2 <CR> Indicates that the software revision level is 3.2
ERROR – Error Codes
The RTA-RS232 will provide error codes when an error is detected.
~ERROR,[Err #]<CR>
Err #
Example:
~ERROR,2<CR> The last command processed was invalid, either syntax or range.
28
RadioTouch
Setup Guide for RTA-RS232
TM
Data
L, S, C, -
HW, SW
ON, OFF
ON, OFF
1
Non-Configuration Command issued while in Configuration Mode
2
Invalid Command
3
Wrong Zone Type
4
Buffer Full
5
Bad EEPROM
6
Configuration Command issued while not in Configuration Mode