Sps - Set Preset; Phc - Photosensor Calibration Mode; Ping; Sps This Command Will Program The Indicated Preset Level To The Current Light Level - Lutron Electronics RadioTouch RTA-RS232 Setup And Installation Manual

Hide thumbs Also See for RadioTouch RTA-RS232:
Table of Contents

Advertisement

Device Control Commands
SPS – Set Preset
This command will program the preset level to the current light level or Sivoia
program a preset, DIP Switch #1 on the RadioTouch
(enter Preset Adjust Mode) command must have already been sent. Refer to the RadioTouch
part number 031-200, for more details on programming presets. This command need only be sent once to
program a preset.
The default light intensities for Presets 1-5 on the RF controllers are as follows:
Preset #1
100%
Preset #2
40%
Preset #3
10%
Preset #4
1%
Note: Any changes to Presets 1-5 will be mimicked in all RadioTouch
undesirable, use Presets 6-16. Also, only presets 1-4 can be set for Sivoia
:SPS,[Zone Number],[Preset Number]<CR>
Zone Number
Preset Number
Example:
:SPS,4,3<CR>
PHC – Photosensor Calibration Mode
This command informs the RTA-RS232 to have the intended zone enter or exit Photosensor Calibration Mode.
:PHC,[Zone Number],[Action Type]<CR>
Zone Number
Action Type
Example:
:PHC,7,ENTER<CR>
Note: While in Photosensor calibration Mode, RadioTouch

PING

This command is used in the event that the RTA-RS232 powers up before the Host and the data flow control is
set to Software. In this case, the Host will miss the initial Prompt that the RTA-RS232 issues at power up. It is
possible that the host will then wait for a prompt, and will never receive one. The PING command is a non-
intrusive way to kick start data flow. When the RTA-RS232 receives the PING command, it simply responds with a
PROMPT.
:PING<CR>
Example:
:PING<CR>
!<CR>
TM
0 – 9
Affected Zone
1 – 16
Preset Number to be programmed
Programs preset #3 on Zone #4
0 – 9
Affected Zone
ENTER
Enters Photosensor Calibration Mode
EXIT
Exits Photosensor Calibration Mode
Tells Zone #7 to enter Photosensor Calibration Mode
PING Command sent to RTA-RS232
Reply from RTA-RS232
Shade position. In order to
®
RF Controller needs to be in the down position or the PSA
ON
OFF
transmitters in the room. If this is
TM
Shades.
®
Controllers will not respond to preset commands.
TM
RadioTouch
Setup Guide for RTA-RS232
TM
Installer's Guide,
TM
Preset #5
100%
25

Advertisement

Table of Contents
loading