SECTION 13 - DRaWOUT CaSE OPTION fOR ThE
MP-3000 MOTOR PROTECTION RELay
CaUTION
COMPLETELy REaD aND UNDERSTaND ThIS INSTRUC-
TION BOOK BEfORE aTTEMPTING INSTaLLaTION,
OPERaTION, OR aPPLICaTION Of ThE EQUIPMENT.
IN aDDITION, ONLy QUaLIfIED PERSONS ShOULD BE
PERMITTED TO PERfORM aNy WORK aSSOCIaTED
WITh ThE EQUIPMENT. aNy WIRING INSTRUCTIONS
PRESENTED IN EIThER DOCUMENT MUST BE fOL-
LOWED CLOSELy. faILURE TO DO SO COULD CaUSE
PERMaNENT EQUIPMENT DaMaGE.

13.0 Introduction

This section describes the Drawout Case option for the MP-3000
Motor Protection Relay.
The basic operation of the MP-3000 relay is applicable to all styles
of the drawout case. Table 13.1 lists the Drawout Case versions.
Table 13.1 Ordering Information.
Description
MP-3000 Drawout Relay, 5 A,
No Communications
MP-3000 Drawout Relay, 5 A, Built-in
INCOM Communications
MP-3000 Drawout Relay, 5 A,
Modbus
MP-3000 Drawout Relay, 5 A,
DeviceNet
MP-3000 Drawout Relay, 1 A,
No Communications
MP-3000 Drawout Relay, 1 A, Built-in
INCOM Communications
MP-3000 Drawout Relay, 1 A,
Modbus
MP-3000 Drawout Relay, 5 A,
DeviceNet
MP-3000 Drawout Outer Chassis, for
Use with No Communicatiions or IN-
COM Communications Inner Chassis
MP-3000 Drawout Outer Chassis, for
Use with Modbus Communicatiions
Inner Chassis
MP-3000 Drawout Outer Chassis, for
Use with DeviceNet Communicatiions
Inner Chassis

13.1 General Description

The Quick Release Drawout Case permits the relay to be removed
from service without disconnecting the wires. The MP-3000 Drawout
MP-3000
Relay maintains the same electrical and operating specifications as
the standard MP-3000. Specifications for the Drawout connectors are
shown in Table 13.2.
Make/Break Rating
Terminal Wire Gauge
Screw Torque Requirements
The MP-3000 Drawout consists of two assemblies: an inner chassis
and an outer chassis. The outer chassis consists of an aluminum
housing with terminal blocks, a molded plastic flange with quick-re-
lease actuators, and a locking mechanism.
The drawout terminal blocks feature self-shorting, or short-before-
break set of contacts, for CT connections that maintain circuit continu-
ity when the device is removed. These self-shorting contacts prevent
damaging voltages from existing across the current transformer
windings.
Catalog Number
An extra set of self-shorting terminals can be used to keep the motor
running while the relay is out of its case, or to provide a No Protection
MP-3011
Alarm (refer to Subsection 13.4 for more information).

13.2 Installation

MP-3012
MP-3013
MP-3014
The following material supplements installation information provided in
Sections 6.1.1 through 6.1.3 and Figures 6.1 and 6.3. Refer to these
sections and figures first.
MP-3111
13.2.1 Panel Preparation
MP-3112
The Drawout Case uses the same panel cutout as the fixed mount
MP-3000, IQ1000II, and IQ1000. When mounting the Drawout Case
in a panel, it is necessary to prepare a cutout for the device per Figure
MP-3113
13.1. If a standard IQ cutout exists, no additional panel setup is re-
quired. The Drawout mounts securely in an existing 6-hole or 10-hole
cutout.
MP-3114
13.2.2 MP-3000 Drawout Relay Parts List
MP3X11-OC
Before mounting the Drawout Relay, check the contents of the box
against the parts listed in Table 13.3 and shown in Figure 13.2.
MP3X13-OC
MP3X14-OC
MP-3000 Drawout Inner Chassis
MP-3000 Drawout Outer Case
Outer Flange
Mounting Hardware – #10-32 nuts and
lock washers
MP-3000 Instruction CD
www.eaton.com
Table 13.2 Drawout Connector Specifications.
Description
10 A @ 240 Vac nominal
0.25 A @ 280 Vdc
maximum
No. 14 to No. 10 AWG
(2.5 mm
18 lb-in. (2.0 Nm)
NOTICE
Table 13.3 MP-3000 Drawout Relay Parts List.
Description
IM02602002E
Value
2
2
to 6.0 mm
)
Quantity
1
1
1
6 each
1