UNIVERSAL RTD
MODULE TERMINALS
3
2
1
CABLE SHIELD WIRE
RTD WIRING (TWO-LEAD TYPE)
3
2
1
RTD WIRING (THREE-LEAD TYPE)
NOTES:
1. CONNECT CABLE SHIELD AT RTD MODULE TERMINALS ONLY. .
CUT SHIELD SHORT AT MOTOR END AND USE SHRINK TUBING
OR ELECTRICAL TAPE TO INSULATE ..
2. RTD
s MUST BE NOT BE GROUNDED AT THE MOTOR, AND NO COMMON
CONNECTIONS BETWEEN INDIVIDUAL RTD ' s SHOULD BE MADE AT
THE MOTOR OR THE MP - 3000 ..
3. TERMINAL 16 OR 32 ON THE RTD MODULE SHOULD BE CONNECTED
TO AN EARTH GROUND ..
figure 6.9 Wiring to URTD Module.