Eaton MP-3000 Instruction Leaflet page 22

Motor protection relay
Hide thumbs Also See for MP-3000:
Table of Contents

Advertisement

IM02602002E
SUB-
LINE #
DISPLAY
MENU
5
Choose:
UB A ON
UB T ON
or
UB OFF
PaGE 8, SP aREL SETTINGS fOR aLaRM RELay OUTPUT CONfIGURaTION
6
Choose:
WD A ON
WD T ON
or
WD OFF
7
Choose:
MB A ON
MB T ON
or
MB OFF
8
Choose:
LB A ON
LB T ON
or
LB OFF
9
Choose:
AX A ON
AX T ON
or
AX OFF
10
Choose:
SX A ON
SX T ON
or
SX OFF
11
Choose:
TBS T ON
or
TBS OFF
12
RTDF ON
or
RTDF OFF
13
RCOM ON
or
RCOM OFF
14
IOCT ON
or
IOCT OFF
15
PH R ON
or
PH R OFF
16
INSQ ON
or
INSQ OFF
17
REMT ON
or
REMT OFF
18
DIFT ON
or
DIFT OFF
19
INCT ON
or
INCT OFF
20
TRNT ON
or
TRNT OFF
21
ZSWT ON
or
ZSWT OFF
22
TBYP ON
or
TBYB OFF
Page
4-10
MP-3000
Table 4.3 View Setting Mode/Program Worksheet.
HELP MESSAGE
ENABLE PHASE UNBALANCE ALARM
OR TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
ENABLE WINDING TEMP ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
ENABLE MOTOR BEARING ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
ENABLE LOAD BEARING ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
ENABLE AUXILIARY RTD TEMP ALARM
OR TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
ENABLE STARTS PER TIME TRIP OR
ALARM TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
ENABLE TIME BETWEEN STARTS TRIP
TO ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
ENABLE INDIVIDUAL RTD CHANNEL
FAILURE TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
ENABLE RTD MODULE
COMMUNICATION FAILURE TO
ACTIVATE ALARM RELAY OR DISABLE
ENABLE INSTANTANEOUS TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
ENABLE PHASE REVERSAL TRIP TO
ACTIVATE ALARM RELAY OUTPUT OR
DISABLE
ENABLE INCOMPLETE SEQUENCE
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
ENABLE REMOTE TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
ENABLE DIFFERENTIAL TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
ENABLE INCOM TRIP TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
ENABLE TRANSITION TRIP TO
ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
ENABLE ZERO SPEED SWITCH TRIP
TO ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
ENABLE TRIP BYPASS TO ACTIVATE
ALARM RELAY OUTPUT OR DISABLE
www.eaton.com
SETTING RANGE/VALUE
(DEfaULT SELECTION aND
VaLUE aS ShIPPED IN BOLD)
UB a ON
Toggles between
, UB T ON, and
UB OFF
WD a ON
Toggles between
, WD T ON, and
WD OFF
MB a ON
Toggles between
, MB T ON, and
MB OFF
LB a ON
Toggles between
, LB T ON, and
LB OFF
aX a ON
Toggles between
, AX T ON, and
AX OFF
SX a ON
Toggles between
, SX T on, and
SX OFF
TBS Off
Toggles between TBS T ON and
RTDf ON
Toggles between
and RTDF OFF
RCOM ON
Toggles between
and RCOM OFF
IOCT Off
Toggles between IOCT ON and
Ph R Off
Toggles between PH R ON and
INSQ Off
Toggles between INSQ ON and
REMT Off
Toggles between REMT ON and
DIfT Off
Toggles between DIFT ON and
INCT Off
Toggles between INCT ON and
TRNT Off
Toggles between TRNT ON and
ZSWT Off
Toggles between ZSWT ON and
TByP Off
Toggles between TBYP ON and
VALUE SELECTED

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents