Eaton MP-3000 Instruction Leaflet page 25

Motor protection relay
Hide thumbs Also See for MP-3000:
Table of Contents

Advertisement

SUB-
LINE #
DISPLAY
MENU
8
Choose:
MB A ON
MB T ON
or
MB OFF
9
Choose:
LB A ON
LB T ON
or
LB OFF
10
Choose:
AX A ON
AX T ON
or
AX OFF
11
Choose:
SX A ON
SX T ON
or
SX OFF
12
Choose:
TBS T ON
or
TBS OFF
13
RTDF ON
or
RTDF OFF
14
RCOM ON
or
RCOM OFF
15
IOC A ON
IOC T ON
or
IOC OFF
16
PH R ON
or
PH R OFF
17
INSQ ON
or
INSQ OFF
18
REMT ON
or
REMT OFF
19
DIFT ON
or
DIFT OFF
20
INCT ON
or
INCT OFF
21
TRNT ON
or
TRNT OFF
22
ZSWT ON
or
ZSWT OFF
23
TBYP ON
or
TBYP OFF
PaGE 11, SP a OUT SETTING fOR aNaLOG OUTPUT CONfIGURaTION
1
MAX 100
MAX 125
MAX WRTD
MAX %I2T
MP-3000
Table 4.3 View Setting Mode/Program Worksheet.
HELP MESSAGE
ENABLE MOTOR BEARING ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
ENABLE LOAD BEARING ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
ENABLE AUXILIARY RTD TEMP ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
ENABLE STARTS PER TIME TRIP OR
ALARM TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
ENABLE TIME BETWEEN STARTS TRIP
TO ACTIVATE AUX2 RELAY OUTPUT
OR DISABLE
ENABLE INDIVIDUAL RTD CHANNEL
FAILURE TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
ENABLE RTD MODULE
COMMUNICATION
FAILURE TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
ENABLE INSTANTANEOUS TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
ENABLE PHASE REVERSAL TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
ENABLE INCOMPLETE SEQUENCE
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
ENABLE REMOTE TRIP TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
ENABLE DIFFERENTIAL TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
ENABLE INCOM TRIP TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
ENABLE TRANSITION TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
ENABLE ZERO SPEED SWITCH TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
ENABLE TRIP BYPASS TO ACTIVATE
AUX2 RELAY OUTPUT OR DISABLE
4-20 MA OUTPUT
MAX 100-20 MA FOR 100% FLA
MAX 125-20 MA FOR 125% FLA
MAX WRTD - 20 MA FOR TRIP LEVEL
MAX %I2T-20MA FOR 100% I2T
www.eaton.com
SETTING RANGE/VALUE
(DEfaULT SELECTION aND
VaLUE aS ShIPPED IN BOLD)
Toggles between MB A ON, MB T ON, and
MB Off
Toggles between LB A ON, LB T ON, and
LB Off
Toggles between AX A ON, AX T ON, and
aX Off
Toggles between SX A ON, SX T ON, and
SX Off
TBS Off
Toggles between TBS T ON and
RTDf Off
Toggles between RTDF ON and
RCOM Off
Toggles between RCOM ON and
IOCT Off
Toggles between IOCT ON and
Ph R Off
Toggles between PH R ON and
INSQ Off
Toggles between INSQ ON and
REMT Off
Toggles between REMT ON and
DIfT Off
Toggles between DIFT ON and
INCT Off
Toggles between INCT ON and
TRNT Off
Toggles between TRNT ON and
ZSWT Off
Toggles between ZSWT ON and
TByP Off
Toggles between TBYP ON and
MaX 125
Select one of MAX 100,
, MAX
WRTD or MAX %I2T
IM02602002E
VALUE SELECTED
Page
4-13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents