IM02602002E
Clock
Accuracy:
IPONI Communications (Section 10 contains more protocols.)
Type:
Baud Rate:
Maximum Distance:
Protocol:
Functions:
Logging
Log Book:
Log Event:
Log Start:
Start Profile:
History Records:
Environmental Ratings
Operating Temperature:
Storage Temperature:
Humidity:
Page
3-2
MP-3000
Free running ± 1 min./mo.
@ 25°C (77°F). Automati-
cally updated by PowerNet
host.
2 wire, 115.2 kHz carrier
1,200 ASK or 9,600 FSK
10,000 feet
INCOM
Read/write set points
Read metered values
Read trip/alarms
Read events
Read history
Reset history
Reset functions
Emergency override
Trip
View starting profile
100 events
20 trips and alarms
Last 4 starts
Last 4 starts (communications
port only)
Motor, trips, alarms, and totals
-20° to +60°C (-4° to +140°F)
-45° to +85°C (-49° to +185°F)
0 to 95% non-condensing
www.eaton.com
Dimensions (fixed Mount Case Only)
Height:
Width:
Depth:
Weight:
Standards
ANSI/IEEE C37.90-1989
Standard for Relay Systems Associated with Electric Power Apparatus.
ANSI/IEEE C37.90.1-1989
Standard Surge Withstand Capability (SWC) Tests for Protective
Relays and Relay Systems
ANSI/IEEE C37.90.2-1995
Standard Withstand Capability of Relay Systems to Radiated
Electromagnetic Interference from Transceivers
UL-1053
Ground Fault Sensing and Relaying Equipment
Emissions (EN-50081-2):
EN 50011 CISPR-11, Class A, CFR 47 FCC Part 15
Subpart b Class A
EN-61000-6-2
Immunity
EN 61000-4-2
ESD
EN 61000-4-3
RF Radiated Immunity
EN 61000-4-4
EFT/Burst Immunity
EN 61000-4-5
Surge Immunity
EN 61000-4-6
RF Conducted Immunity
EN 61000-4-8
Power Frequency Magnetic Field Immunity
EN 61000-4-11
Voltage Variation Immunity
10.25 in. (26.04 cm)
6.72 in. (17.0 cm)
4.3 in. (10.9 cm)
4.0 lbs. (1.8 kg)
7.0 lbs. (3.2 kg) (with URTD
and PONI)