Eaton MP-3000 Instruction Leaflet page 15

Motor protection relay
Hide thumbs Also See for MP-3000:
Table of Contents

Advertisement

Trip
Alarm
Protection
Program
Monitor
View Setting
Display
Complete help Message
READY--1
READY TO START MOTOR, SINGLE
PHASE TEST MODE
READY--3
READY TO START MOTOR, THREE
PHASE TEST MODE
RUN
MOTOR IS RUNNING
START
ATTEMPTING TO START MOTOR
DISARMED
WARNING RELAY IS DISARMED
AND CAN NOT TRIP
ABKSP XX
ANTI-BACKSPIN ACTIVE, REMAIN-
ING MINUTES ACTIVE SHOWN
ILLEGAL
AN ILLEGAL REQUEST WAS MADE
MP-3000
MP-3000
Trip
Alarm
Protection
Aux 1
Program
Aux 2
Monitor
View Setting
History
Page
Line
Emrg
Prog
Over
ride
figure 4.2 MP-3000 LED Indicators.
Table 4.1 Motor State (Default Mode) Display.
MP-3000 has been set to 1 PHASE for bench testing only. Will not
protect a 3-phase motor. Change setting P13L1 to 3 PHASE for
normal motor protection.
Motor is stopped and MP-3000 is ready for a start, 3-phase mode.
Motor is running, as indicated by phase currents.
Motor is starting, and has not yet reached transition to RUN as
defined by User settings.
Protection functions have been blocked from operating the trip relay
by User setting P12L18. MOTOR IS UNPROTECTED. This mode
of operation is for commissioning in a critical process only. Refer to
Section 5.12.18.
The motor is stopped, and the trip contact has been opened to pre-
vent restarting until the antibackspin time delay has expired. XX is
the remaining minutes before restarting is allowed.
Response to request for an action that the relay cannot perform.
Setpoints were not properly stored. Reprogram the unit and save
settings.