Description of device

Overload protection with current transformer-oper-
ated overload relay
The ZB65-.../XTOB...DC1 and ZB150-.../XTOB...GC1 over-
load relays are 3 pole electromechanical overload relays and
are equipped with bimetallic releases. They are suitable both
for AC and for DC operation.
The ZB65-.../XTOB...DC1 and ZB150-.../XTOB...GC1 over-
load relays can be mounted directly onto DIL contactor
relays.
Direct attachment
Overload relays
ZB65-.../XTOB...DC1
ZB150-.../XTOB...GC1
The ZB65/XTOB...DC1 relays can also be operated indivi-
dually in combination with a separate mounting.
The ZB150-...KK/XTOB...GC1S relays are designed for
separate mounting.
Separate positioning
Overload relays
ZB65-.../XTOB...DC1
ZB150-...KK/XTOB...GC1S
In the event of an overload trip, auxiliary contacts 95-96 and
97-98 switch and interrupt the control circuit of the relevant
contactor. In this way, they indirectly disconnect the power
flow of the monitored motor.
Description of device
Contactor
DILM40
XTCE040D
DILM50
XTCE050D
DILM65
XTCE065D
DILM72D
XTCE072D
DILM80
XTCE080F
DILM95
XTCE095F
DILM115
XTCE115G
DILM150
XTCE150G
DILM170
XTCE170G
Separate mounting
ZB65-XEZ/XTOBXDIND
39