Eaton MP-3000 Instruction Leaflet page 80

Motor protection relay
Hide thumbs Also See for MP-3000:
Table of Contents

Advertisement

IM02602002E
Table 10.1 allowed Ranges of MP-3000 Settings for Communications in IQ 1000 II Emulation Mode.
MP-3000
IQ 1000
Setting
II Setting
P2L2
3
Winding temperature trip
P2L4
4
Motor bearing temperature trip
P2L6
5
Load bearing temperature trip
P2L8
6
Auxiliary temperature trip
P2L3
7
Winding temperature alarm
P2L5
8
Motor bearing temperature alarm
P2L7
9
Load bearing temperature alarm
P2L9
10
Auxiliary temperature alarm
P3L1
11
Ground fault trip level
P3L2
12
Ground fault start delay
P3L3
14
Ground fault run delay
P3L5
16
IOC start delay
P1L3
18
Locked rotor time
P1L4
19
Ultimate trip current
P4L2
20
I2T alarm
P4L3
22
Jam alarm
P3L6
23
Jam trip
P3L7
24
Jam start delay
P3L10
28
Underload start delay
P3L11
29
Underload run delay
P4L7
30
Phase unbalance alarm
P5L5
37
Transition current
P5L6
38
Transition time
P5L8
40
Incomplete sequence time
P5L12
41
Antibackspin time
P6L1
46
Program discrete input
P9L1
Through
48
Trip state for AUX1 relay
P9L25
Page
10-4
MP-3000
Setting Description
www.eaton.com
IQ 1000 II Range
(stay within these ranges to
communicate in IQ 2 EN mode)
0-199
C (32-390
F)
°
°
0-199
C (32-390
F)
°
°
0-199
C (32-390
F)
°
°
0-199
C (32-390
F)
°
°
0-199
C (32-390
F)
°
°
0-199
C (32-390
F)
°
°
0-199
C (32-390
F)
°
°
0-199
C (32-390
F)
°
°
1-12 A
1-20 cycles
0-10 cycles
1-20 cycles
1-60 seconds
85-125
60-100%
100-1,200% of FLA
100-1,200% of FLA
0-60 seconds
0-100 seconds
1-10 seconds
10-50%
50-150% FLA
0-240 seconds
1-60 seconds
0-600 seconds (0 means OFF)
REM RST, REM TRIP, DIF TRIP,
MTR STOP, RST DBL
All trips, IOC only, I2T only, GFLT
only, JAM only, UL only, MBT only,
LBT only, WT only, and REV only
MP-3000 Range
(stay within these ranges
to communicate in IQ 2
EN mode)
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF, .2-2,200 A
2-60 cycles
0-60 cycles
2-60 cycles
1-120 seconds
85-150
OFF, 60-99%
OFF
OFF
0-1,200 seconds
0-120 seconds
0-240 seconds
OFF, 4-40%
10-300% FLA
0-480 seconds
OFF, 1-240 seconds
OFF,1-3,600 seconds
EMG OVR, ZERO SW
Fully programmable—
over 4,194,304
possibilities, including
new load shed function

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents