IM02602002E
SUB-
LINE #
DISPLAY
MENU
PaGE 12, SP SyS SETTINGS fOR SySTEM CONfIGURaTION
1
TP MODE X
2
AL MODE X
3
AX1 MOD X
4
AX2 MOD X
5
MAN I2T
or
AUTO I2T
6
RUN PGM
or
STOP PGM
7
EMRG EN
or
EMRG DIS
8
12 HOUR
or
24 HOUR
9
M
D
D
M
10
IQ2 DIS
11
RLYF TRP
RLYF ALM
or
RLYF T+A
12
INCT DIS
or
INCT EN
13
DISARMED
or
ARMED
PaGE 13, SP TEST SETTINGS fOR TESTING INPUTS aND OUTPUTS*
1
3 PHASE
or
1 PHASE
2
TRP ENER
or
TRP DENR
3
ALM ENER
or
ALM DENR
Page
4-14
Table 4.3 View Setting Mode/Program Worksheet.
HELP MESSAGE
CONFIGURE TRIP RELAY OUTPUT TO
BE MODE 1 --
TRIP RELAY ENERGIZES ON TRIP
EVENT OR MODE 2 --TRIP RELAY
ENERGIZES ON POWER UP AND
DE-ENERGIZES ON TRIP EVENT
CONFIGURE ALARM RELAY OUTPUT
TO BE MODE 1 - ALARM RELAY
ENERGIZES ON ALARM EVENT OR
MODE 2 - ALARM RELAY ENERGIZES
ON POWER UP AND DE-ENERGIZES
ON ALARM EVENT
CONFIGURE AUX1 RELAY OUTPUT TO
BE MODE 1 - AUX1 RELAY ENERGIZES
ON AUX1 EVENT OR MODE 2 - AUX1
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON AUX1 EVENT
CONFIGURE AUX2 RELAY OUTPUT TO
BE MODE 1 - AUX2 RELAY ENERGIZES
ON AUX2 EVENT OR MODE 2 - AUX2
RELAY ENERGIZES ON POWER UP
AND DE-ENERGIZES ON AUX2 EVENT
AUTO OR MANUAL I2T RESET
ENABLE UNIT TO BE PROGRAMMED
WHILE MOTOR IS RUNNING
EMERGENCY OVERRIDE ENABLE
EMRG EN - ENABLE EMERGENCY
OVERRIDE
EMRG DIS - DISABLE EMERGENCY
OVERRIDE
SET MONITOR MODE CLOCK DISPLAY
12 HOUR - AM/PM TIME DISPLAYED
24 HOUR - 24 HOUR TIME DISPLAYED
SET REAL TIME DATE DISPLAY -
Y
MONTH DAY YEAR OR
Y
DAY MONTH YEAR
INCOM COMMUNICATIONS MODE
IQ2 EN -IQ1000II EMULATION
IQ2 DIS - MP3000 COMMUNICATION
INTERNAL DIAGNOSTIC FAILURE
ACTIVATES TRIP AND OR ALARM
RELAY
INCOM TRIP DISABLED OR ENABLED
ARM OR DISARM TRIP RELAY
WARNING DISARM WILL NOT ALLOW
TRIP RELAY TO FUNCTION
SINGLE PHASE TEST MODE OR
THREE PHASE PROTECTION MODE
TRP ENER - ENERGIZE TRIP RELAY
TRP DENR - DE-ENERGIZE TRIP RELAY
ALM ENER - ENERGIZE ALARM RELAY
ALM DENR - DE-ENERGIZE ALARM
RELAY
MP-3000
SETTING RANGE/VALUE
(DEfaULT SELECTION aND
VaLUE aS ShIPPED IN BOLD)
Toggles between TP MODE 1 and
Toggles between AL MODE1 and
aX1 MOD1
Toggles between
aX2 MOD1
Toggles between
MaN I2T
Toggles between
Toggles between RUN PGM and
Toggles between EMRG EN and
12 hOUR
Toggles between
M
D
y
or D
M
DIS
Toggles between
and EN
Toggles between RLYF TRP, RLYF ALM and
RLyf T+a
Toggles between INCT DIS and
aRMED
Toggles between
3-PhaSE
Toggles between
NOTE: 1-PHASE is for bench testing ONLY.
Toggles between TRP ENER and TRP DENR
Reset
Press and hold
(none)
selected test
Toggles between ALM ENER AND ALM DENR
Reset
Press and hold
(none)
selected test
www.eaton.com
VALUE SELECTED
TP MODE2
aL MODE2
and AX1 MOD2
and AX2 MOD2
and AUTO I2T
STOP PGM
EMRG DIS
and 24 HOUR
Y
INCT EN
and DISARMED
and 1-PHASE