Eaton MP-3000 Instruction Leaflet page 16

Motor protection relay
Hide thumbs Also See for MP-3000:
Table of Contents

Advertisement

IM02602002E
SUB-
LINE
DISPLAY
MENU
MONT I
1
IAV XXX
2
IA XXX
3
IB XXX
4
IC XXX
5
IG XXX
6
%IA XXX
7
%IB XXX
8
%IC XXX
9
%UB XXX
MONT
RTD
1
WT1 XXX
2
WT2 XXX
3
WT3 XXX
4
WT4 XXX
5
WT5 XXX
6
WT6 XXX
7
MT1 XXXX
8
MT2 XXXX
9
LT1 XXXX
10
LT2 XXXX
11
AXT XXXX
MONT
MTR
1
VER XXXX
2
%I2T XXX
3
TUS XXX
4
RMST XX
5
OST XXX
6
ICM XXXX
7
DI 1 OFF or
DI 1 ON
8
DI 2 OFF or
DI 2 ON
MONT
TIM
1
HH.MM XM
or
HH.MM
2
MM/DD/YY
or
Page
4-4
MP-3000
Table 4.2 Monitor Mode Display.
COMPLETE HELP MESSAGE
MONITOR REAL-TIME VALUES
REAL-TIME DATA FROM CURRENT MEASUREMENTS
AVERAGE CURRENT OF THE THREE PHASES
PHASE A CURRENT IN AMPS
PHASE B CURRENT IN AMPS
PHASE C CURRENT IN AMPS
GROUND FAULT CURRENT IN AMPS
PHASE A CURRENT AS A PERCENT OF FULL LOAD AMPS
PHASE B CURRENT AS A PERCENT OF FULL LOAD AMPS
PHASE C CURRENT AS A PERCENT OF FULL LOAD AMPS
PHASE UNBALANCE - IF POSITIVE THE RATIO OF NEGATIVE
TO POSITIVE SEQUENCE CURRENT - IF NEGATIVE THE
INVERSE
REAL-TIME DATA FROM RTD MODULE
WINDING TEMP 1 IN DEGREES F or C
WINDING TEMP 2 IN DEGREES F or C
WINDING TEMP 3 IN DEGREES F or C
WINDING TEMP 4 IN DEGREES F or C
WINDING TEMP 5 IN DEGREES F or C
WINDING TEMP 6 IN DEGREES F or C
MOTOR BEARING TEMP 1 IN DEGREES
F or C
MOTOR BEARING TEMP 2 IN DEGREES
F or C
LOAD BEARING TEMP 1 IN DEGREES
F or C
LOAD BEARING TEMP 2 IN DEGREES
F or C
AUXILIARY TEMP IN DEGREES F or C
REAL-TIME MOTOR DATA
SOFTWARE VERSION NUMBER
PERCENT OF I2T TRIP LEVEL
TIME IN MINUTES UNTIL NEXT START CAN OCCUR
REMAINING STARTS
TIME LEFT ON OLDEST START IN MINUTES
ADDRESS ON THE IMPACC NETWORK IN HEXADECIMAL
STATE OF DISCRETE INPUT 1
STATE OF DISCRETE INPUT 2
DATE AND TIME
CURRENT TIME
CURRENT DATE
www.eaton.com
DESCRIPTION
Monitor mode
Current monitoring data follows
Average RMS current of 3-phase currents in amps
Actual ac line motor RMS current
Actual ac line motor RMS current
Actual ac line motor RMS current
Actual ground current
Percentage of actual monitored current in amps
Percentage of actual monitored current in amps
Percentage of actual monitored current in amps
Ratio of negative sequence current to positive
sequence current in percent. If a phase reversal
exists, the ratio is inverted and a negative sign is displayed.
RTD monitoring data follows. (Page only visible
when URTD communicates with MP-3000.)
RTD reading - terminals 1, 2, 3
RTD reading - terminals 4, 5, 6
RTD reading - terminals 7, 8, 9
RTD reading - terminals 10, 11, 12
RTD reading - terminals 13, 14, 15
RTD reading - terminals 17, 18, 19
RTD reading - terminals 20, 21, 22
RTD reading - terminals 23, 24, 25
RTD reading - terminals 26, 27, 28
RTD reading - terminals 29, 30, 31
RTD reading - terminals 33, 34, 35
Motor monitoring data follows
MP-3000 software version in use
Percentage of thermal bucket used
Displays largest amount of time in minutes among
three functions: anti-backspin, starts per unit time
and time between starts
Number of starts remaining if starts per time is programmed
Remaining time allowed on oldest start for starts per time if
programmed. If motor start/time is exceeded, this is time in minutes
before restart is permitted.
Address of device if on INCOM communications network; only visible
if on network
Current state of discrete input 1; ON = 120 VAC present, OFF = 120
VAC not present
Current state of discrete input 2; ON = 120 VAC present, OFF = 120
VAC not present
Current date and time with display format as programmed
12-hour format
or
24-hour format
Common format
or