Eaton MP-3000 Instruction Leaflet page 20

Motor protection relay
Hide thumbs Also See for MP-3000:
Table of Contents

Advertisement

IM02602002E
SUB-
LINE #
DISPLAY
MENU
2
GFSD XX
3
GFRD XX
4
IOC XXX
5
IOCSD XX
6
JMT XXX
7
JMSD XX
8
JMTR XX
9
ULT XXX
10
ULSD XXX
11
ULTR XXX
12
UBT XXX
13
UBSD XXX
14
UBTR XXX
PaGE 4, SP aLaRM SETTINGS fOR aLaRM EVENTS
1
GFA XXX
2
I2TA XXX
3
JMA XXX
4
JMAR XXX
5
ULA XXX
6
ULAR XXX
7
UBA XXX
8
UBAR XXX
PaGE 5, SP STaRT SETTINGS fOR STaRT EVENTS
1
ST/T XXX
2
T/ST XXX
3
TBS XXX
4
NOCS X
5
TRNC XXX
6
TRNT XXX
7
Choose:
TRN TIME
TRN I
TRN T+C
TRN T/C
Page
4-8
MP-3000
Table 4.3 View Setting Mode/Program Worksheet.
HELP MESSAGE
GROUND FAULT START DELAY IN
CYCLES
GROUND FAULT RUN DELAY IN CYCLES
INSTANTANEOUS OVERCURRENT IN
% FLA
INSTANTANEOUS OVERCURRENT
START DELAY IN CYCLES
JAM TRIP LEVEL IN % FLA
JAM TRIP AND ALARM START DELAY IN
SECONDS
JAM TRIP RUN DELAY IN SECONDS
UNDERLOAD TRIP LEVEL IN % FLA
UNDERLOAD TRIP AND ALARM START
DELAY IN SECONDS
UNDERLOAD TRIP RUN DELAY IN
SECONDS
PHASE UNBALANCE TRIP LEVEL
PHASE UNBALANCE TRIP AND ALARM
START DELAY IN SECONDS
PHASE UNBALANCE TRIP RUN DELAY IN
SECONDS
GROUND FAULT ALARM LEVEL IN % OF
GROUND CT RATIO NUMERATOR
I2T ALARM LEVEL IN % FULL OF I2T TRIP
CAPACITY
JAM ALARM LEVEL IN % FLA
JAM ALARM RUN DELAY IN SECONDS
UNDERLOAD ALARM LEVEL IN % FLA
UNDERLOAD ALARM RUN DELAY IN
SECONDS
PHASE UNBALANCE ALARM LEVEL
PHASE UNBALANCE ALARM RUN DELAY
IN SECONDS
STARTS PER TIME ALLOWED
TIME ALLOWED FOR STARTS COUNT IN
MINUTES
TIME BETWEEN STARTS IN MINUTES
NUMBER OF COLD STARTS ALLOWED
MOTOR START TRANSITION CURRENT
LEVEL IN %FLA
MOTOR START TRANSITION TIME IN
SECONDS
TRANSITION ON EVENT
TRN TIME - ON TIME ONLY
TRN I - ON CURRENT ONLY
TRN T+C - ON TIME OR CURRENT
TRN T/C - ON TIME AND CURRENT
www.eaton.com
SETTING RANGE/VALUE
(DEfaULT SELECTION aND
VaLUE aS ShIPPED IN BOLD)
(5)
2-60 ac cycles (1 cycle increments)
(2)
0-60 ac cycles (1 cycle increments)
Off
300-1,600%,
(1% increments)
(3)
2-60 ac cycles (1 cycle increments)
(1,000%)
100-1,200%, OFF (1% increments)
(60)
0-1,200 sec. (1 sec. increments)
(60)
0-240 sec. (1 sec. increments)
OFF
6-90%,
(1% increments)
(10)
0-120 sec. (1 sec. increments)
(10)
0-240 sec. (1 sec. increments)
Off
4-40%,
(1% increments)
(10)
0-120 sec. (1 sec. increments)
(2)
0-240 sec. (1 sec. increments)
Off
2-55% OF Ground CT ration numerator,
(1% increments)
) (80)
60-99%, OFF (1% increments
(1,000%)
100-1,200%, OFF (1% increments)
(2)
0-240 sec. (1 sec. increments)
Off
6-90%,
(1% increments)
(10)
0-240 sec. (1 sec. increments)
(10)
4-40%, OFF (1% increments)
(10)
0-240 sec. (1 sec. increments)
(1)
1-10 starts/time (increments of 1)
Off
1-240 minutes,
(1 minute increments)
Off
1-240 minutes,
(1 minute increments)
(1)
1-5 starts (increments of 1)
(130)
10-300% (1% increments)
) (10)
0-1,200 sec. (1 sec. increments
Choose one of the four conditions that determine
a start-to-run transition: TRN TIME, TRN I,
TRN T+C
, or TRN T/C
Refer to settings P5L5 and P5L6.
VALUE SELECTED