Eaton MP-3000 Instruction Leaflet page 21

Motor protection relay
Hide thumbs Also See for MP-3000:
Table of Contents

Advertisement

SUB-
LINE #
DISPLAY
MENU
8
INSQ XXX
9
INSQ TRN
or
INSQ ST
10
LAT XXX
11
ZSW ON
or
ZSW OFF
12
ABK XXXX
PaGE 6, SP DI 1 SETTING fOR DISCRETE INPUT NUMBER 1
1
Choose:
REM RST
REM TRIP
DIF TRIP
MTR STOP
RST DBL
ZERO SW
EMG OVR
PaGE 7, SP DI 2 SETTING fOR DISCRETE INPUT NUMBER 2
1
Choose:
REM RST
REM TRIP
DIF TRIP
MTR STOP
RST DBL
INC SEQ
EMG OVR
PaGE 8, SP aREL SETTINGS fOR aLaRM RELay OUTPUT CONfIGURaTION
1
Choose:
GF A ON
GFT ON
or
GF OFF
2
Choose:
I2T A ON
I2T T ON
or
12T OFF
3
Choose:
JAM A ON
JAM T ON
or
JAM OFF
4
Choose:
UL A ON
UL T ON
or
UL OFF
MP-3000
Table 4.3 View Setting Mode/Program Worksheet.
HELP MESSAGE
INCOMPLETE SEQUENCE REPORT
BACK TIME IN SECONDS ON DISCRETE
INPUT 2
INCOMPLETE SEQUENCE START TIME
EVENT INSQ TRN - START TO RUN
TRANSITION INSQ ST - STOP TO START
TRANSITION
LONG ACCELERATION TIME IN
SECONDS
ZERO SPEED SWITCH ON DISCRETE
INPUT 1 ON OR OFF
ANTI-BACKSPIN DELAY TIME IN
SECONDS
CONFIGURE DISCRETE
INPUT 1 --
REM RESET - REMOTE RESET
REM TRIP - REMOTE TRIP
DIF TRIP - DIFFERENTIAL TRIP
MTR STOP - MOTOR STOP DETECTION
RST DBL - RESET DISABLE
ZERO SW - ZERO SPEED SWITCH TO
GET ANY OTHER
EMG OVR - EMERGENCY OVERRIDE
CONFIGURE DISCRETE INPUT 2 --
REM RST - REMOTE RESET
REM TRIP - REMOTE TRIP
DIF TRIP - DIFFERENTIAL TRIP
MTR STOP - MOTOR STOP DETECTION
RST DBL - RESET DISABLE
INC SEQ - INCOMPLETE SEQUENCE
EMG OVR - EMERGENCY OVERRIDE
ENABLE GROUND FAULT ALARM OR
TRIP TO ACTIVATE ALARM RELAY
OUTPUT OR DISABLE
ENABLE I2T ALARM OR TRIP TO
ACTIVATE ALARM RELAY OUTPUT OR
DISABLE
ENABLE JAM ALARM OR TRIP TO
ACTIVATE ALARM RELAY OUTPUT OR
DISABLE
ENABLE UNDER LOAD ALARM OR TRIP
TO ACTIVATE ALARM RELAY OUTPUT
OR DISABLE
www.eaton.com
SETTING RANGE/VALUE
(DEfaULT SELECTION aND
VaLUE aS ShIPPED IN BOLD)
1-240 sec., OFF (1 sec. increments)
NOTE: Choosing a time value here (not OFF)
also locks P7L1 to INC SEQ and no other choices
are available there. Also, if this is set to OFF, a
later setting of P7L1 to INC SEQ will force a
1 second
setting of
here.
INSQ ST
Toggles between INSQ TRN and
Off
1-200 sec.,
(1 sec. increments)
Danger - Set to OFF unless absolutely needed.
If used, connect zero-speed switch. Refer to
settings P5L11 and P6L1.
ZSW Off
Toggles between ZSW ON and
NOTE: Choosing ZSW ON here also locks
P6L1 to ZERO SW and no other choices are
available there. Also, setting P6L1 to ZERO SW
will force ZSW ON here.
Off
1-3,600 seconds,
(1 sec. increments)
Choose from the seven selections for the function
of Discrete Input 1.
If ZERO SW is selected here, P5L11 will
be forced to ZSW ON.
If P5L11 was already set to ZSW ON,
this setting is automatically set to ZERO.
SW and no other selections are visible.
(REM RST)
Choose from the seven selections for the function
of Discrete Input 2.
INC SEQ
If
is selected here, P5L8 will be
turned on and set to 1 second.
If P5L8 was already set to a time value (not OFF),
this setting is automatically set to INC SEQ
and no other selections are visible.
Gf a ON
Toggles between
, GF T ON, and
GF T OFF
I2T a ON
Toggles between
, I2T T ON, and
I2T OFF
jaM a ON
Toggles between
, JAM T ON, and
JAM OFF
UL a ON
Toggles between
, UL T ON, and
UL OFF
IM02602002E