IM02602002E
SUB-
LINE #
DISPLAY
MENU
16
RCOM ON
or
RCOM OFF
17
IOCT ON
or
IOCT OFF
18
PH R ON
or
PH R OFF
19
INSQ ON
or
INSQ OFF
20
REMT ON
or
REMT OFF
21
DIFT ON
or
DIFT OFF
22
INCT ON
or
INCT OFF
23
TRNT ON
or
TRNT OFF
24
ZSWT ON
or
ZSWT OFF
25
TBYP ON
or
TBYP OFF
PaGE 10, SP aUX2 SETTINGS fOR aUX 2 RELay OUTPUT CONfIGURaTION
1
TRN ON
or
TRN OFF
2
Choose:
GF A ON
GF T ON
or
GF OFF
3
Choose:
I2T A ON
I2T T ON
or
V
4
Choose:
JAM A ON
JAM T ON
or
JAM OFF
5
Choose:
UL A ON
UL T ON
or
UL OFF
6
Choose:
UB A ON
UB T ON
or
UB OFF
7
Choose:
WD A ON
WD T ON
or
WD OFF
Page
4-12
MP-3000
Table 4.3 View Setting Mode/Program Worksheet.
HELP MESSAGE
ENABLE RTD MODULE
COMMUNICATION FAILURE TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
ENABLE INSTANTANEOUS TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
ENABLE PHASE REVERSAL TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
ENABLE INCOMPLETE SEQUENCE
TRIP TO ACTIVATE AUX1 RELAY
OUTPUT OR DISABLE
ENABLE REMOTE TRIP TO ACTIVATE
AUX1 RELAY OUTPUT OR DISABLE
ENABLE DIFFERENTIAL TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
ENABLE INCOM TRIP TO ACTIVATE
AUX1 RELAY OUTPUT OR DISABLE
ENABLE TRANSITION TRIP TO
ACTIVATE AUX1 RELAY OUTPUT OR
DISABLE
ENABLE ZERO SPEED SWITCH TRIP
TO ACTIVATE AUX1 RELAY OUTPUT
OR DISABLE
ENABLE TRIP BYPASS TO ACTIVATE
AUX1 RELAY OUTPUT OR DISABLE
ENABLE TRANSITION OUTPUT IF
ENABLED ALL OTHER FUNCTIONS
FOR AUX 2 ARE DISABLED
ENABLE GROUND FAULT ALARM OR
TRIP TO ACTIVATE AUX 2 RELAY
OUTPUT OR DISABLE
ENABLE I2T ALARM OR TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
ENABLE JAM ALARM OR TRIP TO
ACTIVATE AUX2 RELAY OUTPUT OR
DISABLE
ENABLE UNDERLOAD ALARM OR TRIP
TO ACTIVATE AUX2 RELAY OUTPUT
OR DISABLE
ENABLE PHASE UNBALANCE ALARM
OR TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
ENABLE WINDING TEMP ALARM OR
TRIP TO ACTIVATE AUX2 RELAY
OUTPUT OR DISABLE
www.eaton.com
SETTING RANGE/VALUE
(DEfaULT SELECTION aND
VaLUE aS ShIPPED IN BOLD)
RCOM Off
Toggles between RCOM ON and
IOCT Off
Toggles between IOCT ON and
Ph R Off
Toggles between PH R ON and
INSQ Off
Toggles between INSQ ON and
REMT Off
Toggles between REMT ON and
DIfT Off
Toggles between DIFT ON and
INCT Off
Toggles between INCT ON and
TRNT Off
Toggles between TRNT ON and
ZSWT Off
Toggles between ZSWT ON and
TByP Off
Toggles between TBYP ON and
TRN ON
Toggles between
and TRN OFF.
If TRN is set to OFF then the following SP AUX2
functions are available and visible.
Toggles between GF A ON, GF T ON, and
Gf Off
Toggles between I2T A ON, I2T T ON, and
I2T Off
Toggles between JAM A ON, JAM T ON, and
jaM Off
Toggles between UL A ON, UL T ON, and
UL Off
Toggles between UB A ON, UB T ON, and
UB Off
Toggles between WD A ON, WD T ON, and
WD Off
VALUE SELECTED