Eaton MP-3000 Instruction Leaflet page 19

Motor protection relay
Hide thumbs Also See for MP-3000:
Table of Contents

Advertisement

Program Date
Unit ID/Starter Type
Motor HP
Mfgr.
FLA
LRC
SF
SUB-
LINE #
DISPLAY
MENU
VIEW SP
PaGE 1, SP MOTOR SETTINGS fOR MOTOR CONSTaNTS
1
FLA XXXX
2
LRC XXXX
3
LRT XXX
4
UTC XXX
5
PCT XXXX
6
GCT XXXX
7
FREQ 50
or FREQ 60
8
REV or NON
REV
9
STOP X
PaGE 2, SP RTD SETTINGS fOR RTD INPUTS
1
RTD IN °C
or
RTD in °F
2
WD T XXX
3
WD A XXX
4
MB T XXX
5
MB A XXX
6
LB T XXX
7
LB A XXX
8
AX T XXX
9
AX A XXX
10
DIAG ON
or
DIAG OFF
PaGE 3, SP TRIP SETTINGS fOR TRIP EVENTS
1
GFT XXX
MP-3000
Control Schematic
Work Order #
Serial #
Stall Time/LRT
RTD Type
Table 4.3 View Setting Mode/Program Worksheet.
HELP MESSAGE
VIEW PROGRAM SETTINGS
FULL LOAD AMPS
LOCKED-ROTOR CURRENT % OF FLA
MAXIMUM ALLOWABLE STALL TIME IN
SECONDS
ULTIMATE TRIP CURRENT IN %FLA
PHASE CT RATIO NUMERATOR IN
PRIMARY AMP
GROUND CT RATIO NUMERATOR IN
PRIMARY AMP
50 - FOR 50 HERTZ LINE FREQUENCY
60 - FOR 60 HERTZ LINE FREQUENCY
REVERSING OR NONREVERSING
STARTER
MOTOR STOP CURRENT LEVEL IN
% OF PHASE CT RATIO NUMERATOR
DISPLAYED IN DEGREES °C OR °F
WINDING TEMP TRIP
WINDING TEMP ALARM
MOTOR BEARING TRIP
MOTOR BEARING ALARM
LOAD BEARING TRIP
LOAD BEARING ALARM
AUXILIARY TRIP
AUXILIARY ALARM
ALARM ON RTD FAILURE DIAGNOSTIC
GROUND FAULT TRIP LEVEL IN % OF
GROUND CT RATIO NUMERATOR
www.eaton.com
Accel. Time
Other
SETTING RANGE/VALUE
(DEfaULT SELECTION aND
VaLUE aS ShIPPED IN BOLD)
(10)
10-3,000 amps in 1 amp. increments
(300)
300-1,200% in 1% increments
300)
1-120 sec. in 1 sec. increments (
(1)
85-150% in 1% increments
(10)
10-4,000 A in increments of 1
(50)
10-4,000 A in increments of 1
fREQ 60
Toggles between FREQ 50 and
NON REV
Toggles between REV and
2-20% of phase CT ratio numerator in 1%
(5%)
increments
RTD IN
C
Toggles between
°
and RTD IN °F
0-199°C, OFF/32-390 °F, OFF in 1 increments
(100)
0-199°C, OFF/32-390°F, OFF in 1 increments
(80)
0-199°C, OFF/32-390°F, OFF in 1 increments
(100)
0-199°C, OFF/32-390°F, OFF in 1 increments
(80)
0-199°C, OFF/32-390°F, OFF in 1 increments
(80)
0-199°C, OFF/32-390°F, OFF in 1 increments
(80)
0-199°C, OFF/32-390°F, OFF in 1 increments
(100)
0-199°C, OFF/32-390°F, OFF in 1 increments
(80)
DIaG ON
Toggles between
and DIAG OFF
2-55% OF Ground CT ratio numerator, OFF
(24%)
(1% increments)
IM02602002E
Volts
VALUE SELECTED
Page
4-7